| BUILDING PLAN REVIEW |
| PERMIT: 02061252 |
| ADD: 770 NORTHPOINT PARKWAY# 100 |
| CONT: BUTLER |
| TEL: 832-9700 |
| FL BLD CODE= 2001 FLORIDA BUILDING CODE |
| ARCH: ALAN STRASSLER |
| TELL: (561) 627-0336 |
| |
| 1)704.2.1.4 CORRIDOR PARTITIONS, SMOKE |
| STOP PARTITIONS, HORIZONTAL EXIT PART- |
| ITIONS, EXIT ENCLOSURES, AND FIRE |
| RATED WALLS REQUIRED TO HAVE PROTECTED |
| OPENINGS SHALL BE EFFECTIVELY AND |
| PERMANETLY IDENTIFIED WITH SIGNS OR |
| STENCILING IN A MANNER ACCEPTABLE TO THE |
| AUTHORITY HAVING JURISDICTION. SUCH IDEN |
| TIFICATION SHALL BE ABOVE ANY DECORATIVE |
| CEILING CEILING AND IN CONCEALED SPACES. |
| SUGGESTED WORDING" FIRE & SMOKE BARRIER |
| PROTECT ALL OPENINGS". |
| |
| 2) TABLE 803.3 MINIMUM INTERIOR FINISH |
| CLASSIFICATION; PROVIDE INFORMATION |
| BASED ON INTERIOR FINISH REQUIREMENTS |
| BASED ON OCCUPANCY |
| |
| 3)11-4.1.3(3) GROUND & FLOOR SURFACES |
| ALONG ACCESSIBLE ROUTES & IN ACCESSIBLE |
| ROOMS & SPACES SHALL COMPLY WITH |
| 11-4.5. SEE ADDAAG A4.5.1 (GUIDELINE) |
| A STATIC COEFFICIENT OF FRICTION OF 0.6 |
| IS RECOMENDED FOR ACCESSIBLE ROUTES |
| AND 0.8 FOR RAMPS. |
| |
| 4)1204.2 SURROUNDING MATERIALS; |
| THE WALLS & FLOORS OF ALL PUBLIC REST- |
| ROOMS SHALL BE LINED WITH NONABSORBANT |
| MATERIALS TO A HEIGTH OF 4'-0" ABOVE THE |
| FLOOR. |
| |
| 5)1204.3 SHOWERS. SHOWER COMPARTMENTS |
| SHALL HAVE FLOORS AND WALLS CONSTRUCTED |
| OF SMOOTH, CORROSION RESISTANT AND NON- |
| ABSORBENT WATER-RESISTANT MATERIALS TO A |
| HEIGHT OF NOT LESS THAN 70" ABOVE THE |
| COMPARTMENT FLOOR AT DRAIN. |
| |
| 6) FL BLD CODE 1606.1.5: COMPONENTS & |
| CLADDING, PROVIDE 2 COPIES(3 IF THRESH- |
| OLD OR RESIDENT INSPECTOR) OF PRODUCT |
| TESTING REPORT, SBCCI OR DADE COUNTY |
| REPORT ARE ACCEPTED. EXTERIOR DOOR @ |
| CAFETERIA (119A) PROVIDE (2COPIES) OF |
| EITHER SBCCI OR DADE COUNTY, REPORT TO |
| SUPPORT TRANSOM ABOVE OR SEPERATE |
| REPORT REQUIRED. SEE MULLION IF REQUIRED |
| |
| 7)1707.4.5.1 MULLIONS OCCURRING |
| BETWEEN INDIVIDUAL WINDOW AND GLASS |
| DOOR ASSEMBLIES. TESTING REPORTS ARE |
| REQUIRED BY AN APPROVED TESTING |
| LABORATORY OR BE ENGINEERED. |
| |
| 8)1707.4.5.2 MULLIONS SHALL BE DESIGN- |
| ED TO TRANSFER THE DESIGN PRESSURE LOADS |
| APPLIED BY THE WINDOW OR DOOR ASSEMBLIES |
| TO THE ROUGH OPENING SUBTRATE. |
| |
| |
| 9)3003.7.1 ACCESS TO MACHINE ROOMS |
| AND MACHINERY SPACES. A PERMANENT, SAFE |
| AND CONVENIENT MEANS OF ACCESS TO ELEVA- |
| TOR MACHINE ROOMS AND OVERHEAD MACHINERY |
| SPACES SHALL BE PROVIDED FOR AUTHORIZED |
| PERSONAL. THE MEANS OF ACCESS SHALL NOT |
| BE THROUGH RESTROOMS, DRESSING ROOMS, |
| OR TENANT ( INCLUDING OWNER-OCCUPIED) |
| SPACES. |
| |
| LOOK FOR COMMENTS BY THE OTHER PLAN |
| REVIEW DISCIPLINES THAT MAY BE WRITTEN |
| ON THE APPLICATION, PLANS, OR ATTACHED |
| SEPARATELY. WHEN RESUBMITTING PLANS |
| PLEASE CLEARLY INDICATE THE REVISION AND |
| REMOVE AND REPLACE ANY PAGES AS NECESS- |
| ARY. A TRANSMITTAL LETTER LISTING THE |
| ORIGINAL REVIEW COMMENT NUMBER, WITH A |
| DESCRIPTION OF THE REVISION MADE, IDEN- |
| TIFYING THE SHEET OR SPECIFICATION PAGE |
| WHERE THE CHANGES CAN BE FOUND, WILL |
| HELP TO EXPEDITE YOUR PERMIT. THANK YOU |
| FOR YOUR ANTICIPATED COOPERATION. |