Plan Review Notes
Plan Review Notes For Permit 02061252
Permit Number 02061252
Review Stop B
Sequence Number 1
Notes
Date Text
2002-07-22 00:00:00 
 BUILDING PLAN REVIEW
 PERMIT: 02061252
 ADD: 770 NORTHPOINT PARKWAY# 100
 CONT: BUTLER
 TEL: 832-9700
 FL BLD CODE= 2001 FLORIDA BUILDING CODE
 ARCH: ALAN STRASSLER
 TELL: (561) 627-0336
  
 1)704.2.1.4 CORRIDOR PARTITIONS, SMOKE
 STOP PARTITIONS, HORIZONTAL EXIT PART-
 ITIONS, EXIT ENCLOSURES, AND FIRE
 RATED WALLS REQUIRED TO HAVE PROTECTED
 OPENINGS SHALL BE EFFECTIVELY AND
 PERMANETLY IDENTIFIED WITH SIGNS OR
 STENCILING IN A MANNER ACCEPTABLE TO THE
 AUTHORITY HAVING JURISDICTION. SUCH IDEN
 TIFICATION SHALL BE ABOVE ANY DECORATIVE
 CEILING CEILING AND IN CONCEALED SPACES.
 SUGGESTED WORDING" FIRE & SMOKE BARRIER
 PROTECT ALL OPENINGS".
  
 2) TABLE 803.3 MINIMUM INTERIOR FINISH
 CLASSIFICATION; PROVIDE INFORMATION
 BASED ON INTERIOR FINISH REQUIREMENTS
 BASED ON OCCUPANCY
  
 3)11-4.1.3(3) GROUND & FLOOR SURFACES
 ALONG ACCESSIBLE ROUTES & IN ACCESSIBLE
 ROOMS & SPACES SHALL COMPLY WITH
 11-4.5. SEE ADDAAG A4.5.1 (GUIDELINE)
 A STATIC COEFFICIENT OF FRICTION OF 0.6
 IS RECOMENDED FOR ACCESSIBLE ROUTES
 AND 0.8 FOR RAMPS.
  
 4)1204.2 SURROUNDING MATERIALS;
 THE WALLS & FLOORS OF ALL PUBLIC REST-
 ROOMS SHALL BE LINED WITH NONABSORBANT
 MATERIALS TO A HEIGTH OF 4'-0" ABOVE THE
 FLOOR.
  
 5)1204.3 SHOWERS. SHOWER COMPARTMENTS
 SHALL HAVE FLOORS AND WALLS CONSTRUCTED
 OF SMOOTH, CORROSION RESISTANT AND NON-
 ABSORBENT WATER-RESISTANT MATERIALS TO A
 HEIGHT OF NOT LESS THAN 70" ABOVE THE
 COMPARTMENT FLOOR AT DRAIN.
  
 6) FL BLD CODE 1606.1.5: COMPONENTS &
 CLADDING, PROVIDE 2 COPIES(3 IF THRESH-
 OLD OR RESIDENT INSPECTOR) OF PRODUCT
 TESTING REPORT, SBCCI OR DADE COUNTY
 REPORT ARE ACCEPTED. EXTERIOR DOOR @
 CAFETERIA (119A) PROVIDE (2COPIES) OF
 EITHER SBCCI OR DADE COUNTY, REPORT TO
 SUPPORT TRANSOM ABOVE OR SEPERATE
 REPORT REQUIRED. SEE MULLION IF REQUIRED
  
 7)1707.4.5.1 MULLIONS OCCURRING
 BETWEEN INDIVIDUAL WINDOW AND GLASS
 DOOR ASSEMBLIES. TESTING REPORTS ARE
 REQUIRED BY AN APPROVED TESTING
 LABORATORY OR BE ENGINEERED.
  
 8)1707.4.5.2 MULLIONS SHALL BE DESIGN-
 ED TO TRANSFER THE DESIGN PRESSURE LOADS
 APPLIED BY THE WINDOW OR DOOR ASSEMBLIES
 TO THE ROUGH OPENING SUBTRATE.
  
  
 9)3003.7.1 ACCESS TO MACHINE ROOMS
 AND MACHINERY SPACES. A PERMANENT, SAFE
 AND CONVENIENT MEANS OF ACCESS TO ELEVA-
 TOR MACHINE ROOMS AND OVERHEAD MACHINERY
 SPACES SHALL BE PROVIDED FOR AUTHORIZED
 PERSONAL. THE MEANS OF ACCESS SHALL NOT
 BE THROUGH RESTROOMS, DRESSING ROOMS,
 OR TENANT ( INCLUDING OWNER-OCCUPIED)
 SPACES.
  
 LOOK FOR COMMENTS BY THE OTHER PLAN
 REVIEW DISCIPLINES THAT MAY BE WRITTEN
 ON THE APPLICATION, PLANS, OR ATTACHED
 SEPARATELY. WHEN RESUBMITTING PLANS
 PLEASE CLEARLY INDICATE THE REVISION AND
 REMOVE AND REPLACE ANY PAGES AS NECESS-
 ARY. A TRANSMITTAL LETTER LISTING THE
 ORIGINAL REVIEW COMMENT NUMBER, WITH A
 DESCRIPTION OF THE REVISION MADE, IDEN-
 TIFYING THE SHEET OR SPECIFICATION PAGE
 WHERE THE CHANGES CAN BE FOUND, WILL
 HELP TO EXPEDITE YOUR PERMIT. THANK YOU
 FOR YOUR ANTICIPATED COOPERATION.
 JIM WITMER
 PLAN REVIEW
 TEL: (561)659-8096 EX.8412
 FAX: (561)659-8026