Plan Review Notes
Plan Review Notes For Permit 02061166
Permit Number 02061166
Review Stop R
Sequence Number 2
Notes
Date Text
2002-08-26 00:00:00************BUILDING PROVISO************
  
 1)PROVIDE (2) CURRENT AND COMPLETE
 COPIES OF SBCCI OR METRO-DADE PRODUCT
 APPROVALS FOR:
 - ARCHED TOP FIXED GLASS WINDOWS AS
 SHOWN ON ARCHITECTURAL DRAWINGS
  
 2) PROVIDE A SOIL BEARING CAPACITY TEST
 REPORT SIGNED AND SEALED BY ENGINEER,
 PRIOR TO FIRST INSPECTION.
  
 3) PROVIDE MANUFACTURER'S SPECIFICATIONS
 AND UL LISTING FOR GLASS BLOCK WHICH
 INDICATES A ONE HOUR FIRE RATING.
  
 4) PROVIDE (2) PRODUCT APPROVALS, KEY
 PLANS AND INSTALLATION SCHEDULES
 INDICATING THE SPECIFIC TYPES OF ANCHORS
 TO BE USED FOR STORM PANELS. A SEPARATE
 PERMIT WITH ADDITIONAL FEES IS REQUIRED.
  
 5) PLEASE INDICATE THE INTERNAL PRESSURE
 COEFFICIENT ON THE PLANS FOR FUTURE
 SUBMITTALS. IT IS + OR - .18 FOR
 ENCLOSED STRUCTURES.
  
 6) PLEASE CORRECT THE ROOF SHEATHING
 NAIL SPACING LISTED ON SHEETS GN-1, S-2
 AND S-3 OF THE PLANS FOR FUTURE
 SUBMITTALS. IT IS 6"O.C.INTERMEDIATE AND
 6"O.C.EDGES IN ZONES 1&2 AND 6"O.C.
 INTERMEDIATE AND 4"O.C. EDGES IN ZONE 3.
 SEE CITY AMENDMENTS TO FBC TABLE 2306.1.