Plan Review Notes
Plan Review Notes For Permit 02061162
Permit Number 02061162
Review Stop R
Sequence Number 3
Notes
Date Text
2002-09-04 00:00:00************BUILDING PROVISO************
  
 1) PROVIDE A SIGNED AND SEALED DRAWING
 OR LETTER FROM THE ARCHITECT SPECIFYING
 THE BOLT LENGTH AND EMBEDMENT OF THE
 1-1/8" ANCHOR BOLT FOR THE USP TD7
 CONNECTOR INDICATED FOR THE BUILT UP
 POST ON S-1.
  
 2)PROVIDE (2) CURRENT AND COMPLETE
 COPIES OF SBCCI OR METRO-DADE PRODUCT
 APPROVALS FOR:
 - ARCHED TOP FIXED GLASS WINDOW
 - ENTRY DOOR WITH ONE SIDELITE
  
 3) PLEASE SUBMIT A REVISED KEY PLAN AND
 INSTALLATION SCHEDULE. THE INSTALLATION
 COVER SHEET HAS THE WRONG BUILDING
 HEIGHT AND THE WRONG PRODUCT REPORT. THE
 OPENING SIZES ON THE SCHEDULE DO NOT
 CORRESPOND WITH THE NUMBERED OPENINGS ON
 THE KEY PLAN OR THE ARCHITECTURAL PLANS.