2002-08-02 00:00:00CHECKLIST:
 1-AFTER CORRECTIONS ARE DONE TO ORIGINAL
 DRAWINGS PAY IMPACT FEES. BRING BACK
 STAMPED DRAWINGS AND PAID RECEIPT.
 2-NEED RECORDED NOTICE OF COMMENCEMENT.
 3-UPDATE SURVEY. SEE RECORDED PLAT.
 4-DRAWINGS TO HAVE ALL INFORMATION REQ'D
 BY SEC. 1606.1.7 FBC 2001 (MISSING THE
 INTERNAL PRESSURE COEFFICIENT.
 5-REVISE GABLE ENDS DETAILS AS REQUIRED
 TO COMPLY WITH SEC. 2117 FBC 2001.
 6-NEED ONE HOUR GLASS BLOCK ASSEMBLY AT
 ZERO LOT LINE. PROVIDE UL LISTING AND
 SPECS FOR ONE HR ASSEMBLY.
 NOTE: COORDINATE WITH PRODUCT APPROVAL
 SUBMITTED BY THE CONTRACTOR.
 7-REVISE 2X BUCK DETAIL. SEE SECTION
 1707.4.4.2 FBC 2001.
 8-SEE GARAGE DOOR PRODUCT APPROVAL AND
 REVISE BUCK DETAIL AS REQUIRED.
 9-PROVIDE DETAILS/SPECS FOR CEILING
 INSTALLATIONS AT ENTRY AND REAR PORCH.
 SEE ASTM C-1063 FOR PROPER FASTENERS
 AND METAL LATH.
 10-SPECIFY POSTS TO RECEIVE TRUSS GIRDER
 SEE ROOF FRAMING PLAN.
 11-SPECIFY CONCRETE SLAB JOINTS OR
 SPECIFY SUPPORTS FOR WWM. SEE SECTION
 1909.3 FBC 2001.
 12-IF TAKEN CEILING FANS CREDIT ON THE
 ENERGY CALCS, THEN, SPECIFY ON PLANS
 SIZES AS REQUIRED BY TABLE 6-6 CHAPTER
 13 FBC 2001.
 13-PROVIDE PRODUCT APPROVAL FOR:
 A)ENTRY DOOR WITH ONLY ONE SIDELITE
 ASSEMBLY AS SHOWN ON PLANS.
 B)WINDOW MULLIONS WITH CLIPS AS REQUIRED
 BY SEC. 1707.4.5.2 FBC 2001.
 C)ARCHED WINDOWS AS SHOWN ON PLANS.
 D)SLIDING GLASS DOORS WITH TRANSOM ABOVE
 SINGLE ASSEMBLY AS SHOWN ON PLANS.
 CHECK SIZE AND DESIGN PRESSURES.
 E)GLASS BLOCK. ONE HR ASSEMBLY.
  
 14-SEE PLANS FOR ADDITIONAL COMMENTS AND
 PLEASE RETURN REVIEWED SET TO EXPEDITE
 REVIEW PROCESS.