Plan Review Notes
Plan Review Notes For Permit 02061162
Permit Number 02061162
Review Stop M
Sequence Number 1
Notes
Date Text
2002-07-01 00:00:00PASS/PRIVISO
 1) VARIFY TYPE OF VENTILATION USED FOR
 FRESH AIR.PROVIDE CALCULATIONS FOR
 TYPE OF FRESH AIR USED.BEFOR ROUGH
 INSPECTION
 2) NEED MODEL NUMBER OF EVAP.COIAL FOR
 FINAL INSPECTION
 3) NEED FAN SHUTDOWN FOR FINAL
 INSPECTION
 4) NEED PRESSUR TEST ON FREON LINES FOR
 ROUGH INSPECTION
 PLAN REVIEW BY HAROLD MOSER
 (561)659-8096 EXT.8390