Date |
Text |
2002-09-27 00:00:00 | BUILDING REVIEW APPROVED WITH PROVISO: |
| 1-PROVIDE COMPLETE INFORMATION FOR STORM |
| SHUTTERS UNDER A SEPARATE PERMIT. |
| 2-SHEET A-5: REVISE HEIGHT OF HANDRAIL. |
| SEE SEC. 1007.5.1 FBC 2001. |
| 3-SHEET A-6: A)SPECIFY FIREBLOCKING AT |
| SECTION A/A-6. SEC. 2305.1.4 FBC 2001. |
| B)PROVIDE GENERAL SPECS FOR REQUIRED |
| FIREBLOCKING AT ALL CONCEALED SPACES |
| AS REQUIRED BY SEC. 2305.1.4 FBC 2001. |
| C)GARAGE BUCK DETAIL: SPECIFY LENGTH OF |
| ANCHOR BOLT AND SIZE OF WASHER. SEC. |
| 104.2.1.2 CITY AMENDMENTS TO FBC. |
| 4-SHEET A-7: A)REVISE STAIR KEY NOTE #1. |
| HANDRAIL TO BE BET. 34" AND 36". SEE |
| SEC. 1007.5.1 FBC 2001. |
| B)NOTE #9: CLARIFY SIZE OF LEDGER. SEE |
| STRUCTURAL DRAWINGS. |
| 5-SHEET S-1: REVISE LINTEL SCHEDULE TO |
| MATCH PLANS. CHECK LINTEL NUMBER AND |
| SIZE OF OPENINGS. SEC. 104.2.1.2 CITY |
| AMENDMENTS TO FBC 2001. |
| B)SPECIFY HOW LONG ARE THE ANCHOR BOLTS |
| FOR WOOD COLUMNS BOTTOM CONNECTORS. |
| SEC. 104.2.1.2 CITY AMENDMENTS TO FBC. |
| C)CLARIFY REINFORCING FOR FOOTING F5530. |
| SEE FOOTING SCHEDULE. SEC. 104.2.1.2 |
| CITY AMENDMENTS TO FBC 2001. |
| 6-SHEET S-2: A)REVISE TRUSS CONNECTOR |
| SCHEDULE TO MATCH USP PUBLISHED VALUES |
| PROVIDE ENGINEER'G CALCS FOR DIFFERENT |
| VALUES. SEC. 104.2.1.2 CITY AMENDMENTS |
| B)SPECIFY FIRECUT REQUIREMENTS ON THE |
| STRUCTURAL WALL SECTIONS. SEC. 2305.4 |
| C)TYPICAL CONCRETE MASONRY WALL DETAIL: |
| CLARIFY SIZE OF REINFORCEMENT FOR BB. |
| 1#7 OR 1#5. SEE BEAM SCHEDULE. |
| D)SPECIFY CONNECTORS FOR GIRDER TRUSS AT |
| GARAGE ROOF. |
| E)SECTION 1 AND SECTION 2 HAVE DIFFERENT |
| SPECS. CLARIFY/REVISE AS REQUIRED. |
| SEC. 104.2.1.2 CITY AMENDMENTS TO FBC. |
| 7-SHEET S-3: A)REVISE TRUSS CONNECTOR |
| SCHEDULE. SEE COMMENT A ABOVE. |
| B)ROOF SHEATHING & NAILING NOTE AND |
| DIAPHRAGM SCHEDULE SPECS DON'T MATCH. |
| REVISE/CLARIFY AS REQUIRED. |
| C)CONNECTORS SPECIFIED FOR SOME GIRDER |
| TRUSSES DON'T RESIST CALCULATED UPLIFT |
| LOADS. REVISE AS REQUIRED. SEC. 104.2. |
| 1.2 CITY AMENDMENTS TO FBC 2001. |
| 8-PROVIDE STRUCTURAL DETAIL AT RECESSED |
| WINDOWS TO ALLOW FOR STORM SHUTTERS |
| INSTALLATION. SEE PRODUCT APPROVAL FOR |
| LIMITAIONS AND ADDITIONAL ENGINEERING |
| REQUIRED. SEC. 104.2.1.2 CITY AMEND. |
| 9-IDENTIFY ROOF NAILING ZONES IN ROOF |
| FRAMING PLANS. SEE TABLE 2306.1 CITY |
| AMENDMENTS TO FBC 2001. |