2002-08-12 00:00:00 | BUILDING DENIED |
| |
| 1) A RECORDED COPY OF THE NOTICE OF |
| COMMENCEMENT MUST BE SUBMITTED BEFORE A |
| PERMIT CAN BE ISSUED. |
| |
| 2) FL BLD CODE 1804.2.2 QUESTIONABLE |
| SOILS, WHERE THE BEARING CAPACITY IS |
| NOT DEFINETLY KNOWN OR IS IN QUESTION. |
| PROVIDE A SOIL BEARING REPORT. |
| |
| 3) THE SOIL STATEMENT ON SHEET S1 STATES |
| THAT A SEALED LETTER FROM THE ENGINEER |
| OF RECORD WILL BE SUBMITTED ATTESTING |
| THAT THE SITE HAS BEEN OBSERVED AND THE |
| FOUNDATION CONDITIONS ARE SIMILAR TO |
| THOSE UPON WHICH THE THE DESIGN HAS BEEN |
| BASED. |
| |
| 4) THE BONUS ROOM IS REQUIRED TO BE |
| PERMANETLY MARKED ON THE PLANS THAT IT |
| IS NOT TO BE USED FOR SLEEPING PURPOSES |
| AND THE ROOM CAN NOT HAVE A CLOSET. |
| OPENINGS FROM A GARAGE DIRECTLY INTO A |
| ROOM USED FOR SLEEPING PURPOSES IS NOT |
| PERMITTED PER 2001 FBC SEC.411.2.8. |
| |
| 5) THE WINDOW (H) IN THE FIRST FLOOR |
| BATHROOM IS REQUIRED TO HAVE TEMPERED |
| GLASS PER FBC 2405.2.1 (2). |
| |
| 6) INDICATE ON THE PLANS THAT THE BONUS |
| ROOM WALLS ARE INSULATED. |
| |
| 7) PLEASE CHANGE NOTE 6 UNDER GENERAL |
| NOTES ON SHEET A2 TO REFERENCE THE 2001 |
| FLORIDA PLUMBING CODE. |
| |
| 8) THE CONDITIONED AREA LISTED ON THE |
| ENERGY CALCULATIONS DIFFERS FROM THE |
| A/C AREA GIVEN ON THE PLANS. PLEASE |
| CORRECT. |
| |
| 9) SHEET S-2 INDICATES A P3 COLUMN BELOW |
| THE FLOOR TRUSSES,HOWEVER, NOTHING IS |
| SHOWN AT THIS LOCATION ON THE FOUNDATION |
| PLAN ON S-1. PLEASE CLARIFY. SHEET A-1 |
| INDICATES A STRUCTURAL COLUMN,#33 IN THE |
| KEY NOTES AT THIS LOCATION. |
| |
| 10) FL BLDG 1909.3 (EXEPTION# 2) |
| CONCRETE SLABS ON GRADE CONTAINING 6X6/ |
| W1.4XW1.4 WELDED WIRE REINFORCEMENT |
| FABRIC LOCATED IN THE MIDDLE TO THE |
| UPPER 1/3RD OF THE SLAB SHALL BE SUP- |
| PORTED BY APPROVED MATERIALS OR SUPPORTS |
| AT SPACING NOT TO EXCEED 3 FT OR IN |
| ACCORDANCE WITH MANUFACTURER'S SPEC. |
| PLEASE INDICATE ON PLANS. |
| |
| 11) 2305.2.2 FLOOR/CEILING ASSEMBLIES |
| SINGLE FAMILY DWELLINGS. IN FLOOR/CEIL- |
| ING ASSEMBLIES SEPERATING USEABLE SPACE |
| INTO 2 OR MORE APPROXIMATE AREAS WITH NO |
| AREA GREATER THAN 500 SQ FT. DRAFTSTOP- |
| PING SHALL BE PROVIDED PARALLEL TO THE |
| MAIN FRAMING MEMBERS. PLEASE INDICATE |
| THE LOCATIONS AND MATERIALS THAT WILL BE |
| USED ON THE PLANS. |
| |
| 12) SECTIONS #1 AND #3 ON S-2 SHOW A |
| CONCRETE TIE BEAM WITH FOUR REINFORCING |
| BARS. THE REST OF THE PLANS INDICATE |
| SINGLE BEAM BLOCK WITH ONE BAR. PLEASE |
| CLARIFY. |
| |
| 13) PROVIDE (2) CURRENT AND COMPLETE |
| COPIES OF SBCCI OR METRO-DADE PRODUCT |
| APPROVALS FOR: |
| - DOUBLE ENTRY DOORS (THE ONES SUBMITTED |
| ARE ILLEGIBLE) |
| - SINGLE HUNG WINDOWS (THE COVER SHEET |
| DOES NOT MATCH THE REST OF THE PAGES, |
| WHICH ARE EXPIRED) |
| - MULLIONS (EXPIRED) |
| |
| 14) STORM PANELS: NO INSTALLATION |
| SCHEDULE WAS SUBMITTED. THE KEY PLAN IS |
| FOR A GARAGE LEFT MODEL AND THIS IS A |
| GARAGE RIGHT MODEL. THE OPENING SIZES |
| ON THE PLANS DIFFER FROM THOSE ON THE |
| KEY PLAN. PLEASE CORRECT. |
| |
| 15) THE NAILS AND SPACING LISTED FOR THE |
| FLOOR ON SECTION 2 ON SHEET S-2 DOES NOT |
| CORRESPOND WITH THE FLOOR DIAPHRAGM |
| NAILING SPECIFIED IN THE SCHEDULE. |
| |
| ROBERT MCDOUGAL |
| BLDG. PLAN REVIEW |
| (561)659-8096 EXT.8202 |