2002-08-12 00:00:00BUILDING DENIED
  
 1) A RECORDED COPY OF THE NOTICE OF
 COMMENCEMENT MUST BE SUBMITTED BEFORE A
 PERMIT CAN BE ISSUED.
  
 2) FL BLD CODE 1804.2.2 QUESTIONABLE
 SOILS, WHERE THE BEARING CAPACITY IS
 NOT DEFINETLY KNOWN OR IS IN QUESTION.
 PROVIDE A SOIL BEARING REPORT.
  
 3) THE SOIL STATEMENT ON SHEET S1 STATES
 THAT A SEALED LETTER FROM THE ENGINEER
 OF RECORD WILL BE SUBMITTED ATTESTING
 THAT THE SITE HAS BEEN OBSERVED AND THE
 FOUNDATION CONDITIONS ARE SIMILAR TO
 THOSE UPON WHICH THE THE DESIGN HAS BEEN
 BASED.
  
 4) THE BONUS ROOM IS REQUIRED TO BE
 PERMANETLY MARKED ON THE PLANS THAT IT
 IS NOT TO BE USED FOR SLEEPING PURPOSES
 AND THE ROOM CAN NOT HAVE A CLOSET.
 OPENINGS FROM A GARAGE DIRECTLY INTO A
 ROOM USED FOR SLEEPING PURPOSES IS NOT
 PERMITTED PER 2001 FBC SEC.411.2.8.
  
 5) THE WINDOW (H) IN THE FIRST FLOOR
 BATHROOM IS REQUIRED TO HAVE TEMPERED
 GLASS PER FBC 2405.2.1 (2).
  
 6) INDICATE ON THE PLANS THAT THE BONUS
 ROOM WALLS ARE INSULATED.
  
 7) PLEASE CHANGE NOTE 6 UNDER GENERAL
 NOTES ON SHEET A2 TO REFERENCE THE 2001
 FLORIDA PLUMBING CODE.
  
 8) THE CONDITIONED AREA LISTED ON THE
 ENERGY CALCULATIONS DIFFERS FROM THE
 A/C AREA GIVEN ON THE PLANS. PLEASE
 CORRECT.
  
 9) SHEET S-2 INDICATES A P3 COLUMN BELOW
 THE FLOOR TRUSSES,HOWEVER, NOTHING IS
 SHOWN AT THIS LOCATION ON THE FOUNDATION
 PLAN ON S-1. PLEASE CLARIFY. SHEET A-1
 INDICATES A STRUCTURAL COLUMN,#33 IN THE
 KEY NOTES AT THIS LOCATION.
  
 10) FL BLDG 1909.3 (EXEPTION# 2)
 CONCRETE SLABS ON GRADE CONTAINING 6X6/
 W1.4XW1.4 WELDED WIRE REINFORCEMENT
 FABRIC LOCATED IN THE MIDDLE TO THE
 UPPER 1/3RD OF THE SLAB SHALL BE SUP-
 PORTED BY APPROVED MATERIALS OR SUPPORTS
 AT SPACING NOT TO EXCEED 3 FT OR IN
 ACCORDANCE WITH MANUFACTURER'S SPEC.
 PLEASE INDICATE ON PLANS.
  
 11) 2305.2.2 FLOOR/CEILING ASSEMBLIES
 SINGLE FAMILY DWELLINGS. IN FLOOR/CEIL-
 ING ASSEMBLIES SEPERATING USEABLE SPACE
 INTO 2 OR MORE APPROXIMATE AREAS WITH NO
 AREA GREATER THAN 500 SQ FT. DRAFTSTOP-
 PING SHALL BE PROVIDED PARALLEL TO THE
 MAIN FRAMING MEMBERS. PLEASE INDICATE
 THE LOCATIONS AND MATERIALS THAT WILL BE
 USED ON THE PLANS.
  
 12) SECTIONS #1 AND #3 ON S-2 SHOW A
 CONCRETE TIE BEAM WITH FOUR REINFORCING
 BARS. THE REST OF THE PLANS INDICATE
 SINGLE BEAM BLOCK WITH ONE BAR. PLEASE
 CLARIFY.
  
 13) PROVIDE (2) CURRENT AND COMPLETE
 COPIES OF SBCCI OR METRO-DADE PRODUCT
 APPROVALS FOR:
 - DOUBLE ENTRY DOORS (THE ONES SUBMITTED
 ARE ILLEGIBLE)
 - SINGLE HUNG WINDOWS (THE COVER SHEET
 DOES NOT MATCH THE REST OF THE PAGES,
 WHICH ARE EXPIRED)
 - MULLIONS (EXPIRED)
  
 14) STORM PANELS: NO INSTALLATION
 SCHEDULE WAS SUBMITTED. THE KEY PLAN IS
 FOR A GARAGE LEFT MODEL AND THIS IS A
 GARAGE RIGHT MODEL. THE OPENING SIZES
 ON THE PLANS DIFFER FROM THOSE ON THE
 KEY PLAN. PLEASE CORRECT.
  
 15) THE NAILS AND SPACING LISTED FOR THE
 FLOOR ON SECTION 2 ON SHEET S-2 DOES NOT
 CORRESPOND WITH THE FLOOR DIAPHRAGM
 NAILING SPECIFIED IN THE SCHEDULE.
  
 ROBERT MCDOUGAL
 BLDG. PLAN REVIEW
 (561)659-8096 EXT.8202