Plan Review Notes
Plan Review Notes For Permit 02061133
Permit Number 02061133
Review Stop P
Sequence Number 1
Notes
Date Text
2002-06-24 00:00:00DENIED
 REFERENCE: FBC-2001 FUEL GAS
  
 1. SUBMIT CALCULATIONS FOR COMBUSTION
 AIR (IF APPLICABLE) PER FBC-2001 FUEL
 GAS CODE SEC. 304.
 2. SUBMIT MANUFACTURE SHEETS FOR ALL GAS
 EQUIPMENT TO VERIFY COMPLIANCE WITH
 STANDARDS NFPA 54, NFPA 58, AND THE FBC-
 2001 FUEL GAS CODE SEC 402.2.
 3) CHECK PIPE SIZES - NEED TO CHANGE
 SIZE TO EXISTING RANGE, AND NEED 1" FROM
 METER IF GALVANIZED.
  
 REVIEW BY KEN STEVENS
 (561) 659-8096 EXT 8377