| BUILDING PLAN REVIEW |
| PERMIT: 02061099 |
| ADD: 3729 VICTORIA RD |
| CONT: M/I HOMES INC |
| TEL: (561)471-3440 |
| FL BLD CODE= 2001 FLORIDA BUILDING CODE |
| |
| 1) PROVIDE NOC RECORDED WITH THE CLERK |
| OF COURT BEFORE A PERMIT CAN BE ISSUED. |
| |
| 2)2001 FL BLD CODE, 1005.4: |
| PROVIDE EMERGENCY EGRESS WINDOWS IN |
| SLEEPING ROOMS WITH A MINIMUM NET CLEAR |
| OPENING HEIGTH OF 24" AND NET CLEAR |
| OPENING WIDTH OF 20" AND A NET CLEAR |
| OPENING AREA OF 5.7 SQ.FT. GROUND FLOOR |
| OPENINGS ARE PERMITTED TO HAVE A NET |
| CLEAR OPENING OF 5.0 SQ. FT. SILL HEIGTH |
| SHALL NOT BE MORE THAN 44 " ABOVE THE |
| FINISH FLOOR. |
| SHEET 1 OF 7 FRONT ELEVATION VS LEFT |
| ELE. FOR BEDROOM # 3 DETAIL WINDOW SILL |
| AND ROOF FLASHING AND MAINTAIN 44" TO |
| SILL? |
| |
| 3)1204.3 SHOWERS. SHOWER COMPARTMENTS |
| SHALL HAVE FLOORS AND WALLS CONSTRUCTED |
| OF SMOOTH, CORROSION RESISTANT AND NON- |
| ABSORBENT WATER-RESISTANT MATERIALS TO A |
| HEIGHT OF NOT LESS THAN 70" ABOVE THE |
| COMPARTMENT FLOOR AT DRAIN. |
| |
| 4)1204.4 JOINTS. BUILT IN TUBS WITH |
| SHOWERS SHALL HAVE WATER-PROOF JOINTS |
| BETWEEN THE TUB & WATER RESISTANT WALL. |
| |
| 5)1503.4.4 PROTECTION AGAINST DECAY & |
| TERMITES. CONDENSATE LINES & ROOF DOWN |
| SPOUTS SHALL DISCHARGE AT LEAST 1 FT. |
| AWAY FROM THE STRUCTURE SIDEWALL, |
| WHETHER BY UNDERGROUND PIPING, TAIL EX- |
| TENSIONS, OR SPLASH BLOCKS. |
| |
| 6)FIGURE 1606 WIND-BORNE DEBRIS |
| REGION; INDICATES THAT W.P.B. CITY OF IS |
| LOCATED IN THE 140 MPH ZONE. PLANS ARE |
| TO INDICATE THIS. |
| |
| 7)FL. BLD CODE 1606.1.7 THE FOLLOWING |
| INFORMATION RELATED TO WIND SHALL BE |
| SHOWN ON THE CONSTRUCTION DRAWINGS, |
| 1)- BASIC WIND SPEED, MPH |
| 2)- WIND IMPORTANCE FACTOR, & BUILDING |
| CATEGORY |
| 3)- WIND EXPOSURE |
| 4)- INTERNAL PRESSURE COEFFICIENT, |
| 5)- COMPONENTS & CLADDING, THE DESIGN |
| WIND PRESSURES IN TERMS OF PSF. |
| SHEET 1 OF 7 LOADS ON ROOF, ABOVE |
| ARE THE VALUES/ LOADS THE TOTAL BUILDING |
| IS TO DESIGNED TO NOT JUST THE ROOF. |
| THE INTERNAL PRESSURE COEFFICIENT |
| SHOULD READ 0.18! |
| |
| 8) FL BLD CODE 1606.1.5: COMPONENTS & |
| CLADDING, PROVIDE 2 COPIES(3 IF THRESH- |
| OLD OR RESIDENT INSPECTOR) OF PRODUCT |
| TESTING REPORT, SBCCI OR DADE COUNTY |
| REPORT ARE ACCEPTED. |
| FOR THIS JOB PRODUCT REPORT FOR |
| ALUMINIUM HORIZONTAL ROLLING WINDOWS IS |
| OK, EXPIRED AFTER APPLICATION DATE, |
| REPLACE UNDER NEW PERMIT APPLICATION. |
| |
| 9)SITE SPECIFIC ENGINEERING (PRODUCT |
| APPROVAL) REQUIRES THE WET SIGNATURE, |
| DATE AND EMBOSSED SEAL OF THE ENGINEER |
| CERTIFYING THE PRODUCT AND SIGNATURE |
| AND SEAL OF THE DESIGN PROFESSIONAL |
| OF RECORD. THE DESIGN PROFESSIONAL OF |
| RECORD FOR THIS PRODUCT HAS NOT SIGNED & |
| SEALED THE RIGHT PORTION OF THIS AFFIDAV |
| IT, NOR SUPPLIED A SIGNED & SEALED COVER |
| SHEET APPROVING THIS APPLICATION IN |
| THIS SPECIFIC UNIT, (NO ADDRESS). |
| THE ENGENEERING SHEETS ARE NOT HIGH- |
| LIGHTED SHOWING WHAT DETAILS ARE BEING |
| USED, WHAT TYPE OF ANCHOR BEING USED? |
| THERE IS NO KEY PLAN IDENTIFYING WHAT |
| WINDOW IS #1 IS THIS CONCRETE, FILLED |
| CELL OR WOOD? |
| |
| 10) NONE OF THE PRODUCT TESTING REPORTS |
| CAN BE USED SINCE THE WINDOW NOR DOOR |
| PRESSURES ARE GIVEN, THE NOTE COMPONENTS |
| & CLADDING INDICATE A -68.1 PRESSURE???? |
| THE PRODUCT TESTING PRESSURES ARE TO LOW |
| |
| 11)SBCCI REPORT 2139, SPECIFY WHICH |
| DOOR ASSEMBLY SHALL BE USED. |
| HIGHLIGHT MODEL NUMBER. |
| |
| 12) NOTE 7 DOES NOT LIST NAILING REQUIRE |
| MENTS FOR ZONE 3, WHICH APPLIES TO THE |
| GABLE ENDS.CITY AMENDMENTS 2306.1.REVISE |
| NOTE # 7. |
| |
| 13) SHEET# 1 "ROOF NOTES"-8 REFERS TO |
| " C & SE" ZONES, PLEASE EXPLAIN?? |
| |
| 14) SHEET # 1 INDICATES (2) SECTION A'S |
| ONE A FRONT VIEW THE OTHER A SIDE VIEW? |
| |
| 15) SHEET 2 OF 7 FOUNDATION DETAIL FOR |
| SHOWER THIS IN THE 2 STORY SECTION OF |
| THE BUILDING THE DETAIL HAS NO DIMENSION |
| INDICATING HEIGTH OR WIDTH AS DEPICTED |
| IT ISN'T 20" WIDE. |
| |
| 16) THE SAME SHEET FOUNDATION DETAIL# 12 |
| INDICATES THE USE OF A 6" SLEEVE, WHAT |
| ISN'T GIVEN IS THE MINIMUM HEIGTH OF |
| 19 1/2 " EXT DIA.X 3. 1907.3.5(1) |
| |
| 17)2804.4.1 FACTORY-BUILT CHIMNEYS |
| FACTORY BUILT CHIMNEYS SHALL BE LISTED |
| AND SHALL BE INSTALLED IN ACCORDANCE |
| WITH THE CONDITIONS OF THE LISTING, AND |
| MANUFACTURER'S INSTRUCTION. |
| |
| 18)CHIMNEYS FOR THE USE WITH FACTORY- |
| BUILT FIREPLACES SHALL MEET THE |
| REQUIREMENTS OF UL 127. |
| |
| 19)2806.1.2 FACTORY BUILT FIREPLACES |
| SHALL BE TESTED IN ACCORDANCE WITH AND |
| MEET THE REQUIREMENTS OF UL 127. |
| |
| 20)2810 FRESH AIR INTAKES, FRESH AIR |
| INTAKESSHALL BE SCREENED WITH A CORRO- |
| SION RESITANT MATERIAL NOT LARGER THAN |
| 1/2 INCH MESH. FRESH AIR INTAKES SHALL |
| NOT BE TAKEN FROM A LOCATION CLOSER THAN |
| 10 FT FROM ANY CHIMNEY OR VENT OUTLET OR |
| SANITARY SEWER VENT OUTLET, UNLESS SUCH |
| VENT IS NOT LESS THAN 24" ABOVE THE |
| FRESH AIR VENT. FRESH AIR INTAKE VENTS |
| LOCATED ON THE ROOFS WILL BE PROPERLY |
| MARKED WITH A UNIVERSAL MARKING, |
| ***"INTAKE"***, PERMANETLY ATTACHED. |
| SEE 705.1.1.4 FOR FIRE PROTECTION. |
| |
| LOOK FOR COMMENTS BY THE OTHER PLAN |
| REVIEW DISCIPLINES THAT MAY BE WRITTEN |
| ON THE APPLICATION, PLANS, OR ATTACHED |
| SEPARATELY. WHEN RESUBMITTING PLANS |
| PLEASE CLEARLY INDICATE THE REVISION AND |
| REMOVE AND REPLACE ANY PAGES AS NECESS- |
| ARY. A TRANSMITTAL LETTER LISTING THE |
| ORIGINAL REVIEW COMMENT NUMBER, WITH A |
| DESCRIPTION OF THE REVISION MADE, IDEN- |
| TIFYING THE SHEET OR SPECIFICATION PAGE |
| WHERE THE CHANGES CAN BE FOUND, WILL |
| HELP TO EXPEDITE YOUR PERMIT. THANK YOU |
| FOR YOUR ANTICIPATED COOPERATION. |
| JIM WITMER |
| PLAN REVIEW |
| TEL: (561)659-8096 EX.8412 |
| FAX: (561)659-8026 |