Plan Review Notes For Permit 02061052 |
Permit Number |
02061052 |
|
Review Stop |
M |
Sequence Number |
2 |
|
Notes |
Date |
Text |
2002-09-25 00:00:00 | DENIED: | | | | AS PER 2001 FBC 411.5.4, REPAIR GARAGES | | SHALL BE CONTINUOUSLY VENTILATED BY A | | MECHANICAL SYSTEM.AS THE GARAGE IS | | "OPEN" A POSITIVE MEANS IS NOT REQUIRED, | | A MECHANICAL EXHAUST SYSTEM IS REQUIRED | | AND SHALL EXHASUT AT LEAST 0.75 CFM PER | | SQ FT OF FLOOR AREA, CONTROLLED FROM A | | LOCATION CLOSE TO THE ENTRANCE DOOR. | | | | IF YOU HAVE ANY QUESTIONS, PLEASE | | CONTACT PATTY KRAUSS AT 659-8096 | | EXT. 8388. |
|