| BUILDING PLAN REVIEW |
| PERMIT: 02061052 |
| ADD: 3001 OKEECHOBEE BLVD |
| CONT: POPPER & ASSOCIATES |
| TEL: (561)582-3200 |
| FL BLD CODE= 2001 FLORIDA BUILDING CODE |
| |
| 1) 1606.1.4.1 IS THIS BUILDING DESIGNED |
| AS AN OPEN BUILDING OR PARTIALLY |
| ENCLOSED? |
| |
| 2)FL. BLD CODE 1606.1.7 THE FOLLOWING |
| INFORMATION RELATED TO WIND SHALL BE |
| SHOWN ON THE CONSTRUCTION DRAWINGS, |
| 1)- BASIC WIND SPEED, MPH |
| 2)- WIND IMPORTANCE FACTOR, & BUILDING |
| CATEGORY |
| 3)- WIND EXPOSURE |
| 4)- INTERNAL PRESSURE COEFFICIENT, |
| 5)- COMPONENTS & CLADDING, THE DESIGN |
| WIND PRESSURES IN TERMS OF PSF. |
| MISSING THE (4) INTERNAL PRESSURE |
| COEFFICIENT, ENCLOSED RESTROOM. |
| |
| 3) SHEETA-101 DOOR B101, DOES THIS DOOR |
| SERVE AN OCCUPANT LOAD OF 50 OR GREATER? |
| |
| 4) 4.11.5 REPAIR GARAGES. (4) REPAIR |
| GARAGES SHALL BE CONTINUOUSLY VENTILATED |
| BY A MECHANICAL SYSTEM WITH POSITIVE |
| MEANS FOR BOTH INLET AND EXHAUST OF AT |
| LEAST 0.75 CFM PER SQ FT OF FLOOR AREA, |
| CONTROLLED FROM A LOCATION CLOSE TO THE |
| ENTRANCE DOORS. |
| |
| 5) MEZZANINE, ABOVE THE VESTIBULE AND |
| RESTROOM, PROVIDE ADDITIONAL INFORMATION |
| USEAGE, IF NOT STORAGE VERTICAL ACCESS |
| IBILITY SHALL BE ADDRESSED. IF FOR |
| STORAGE ACCESSIBILITY? |
| |
| 6)106.4.2 STORAGE & FACTORY- INDUS- |
| TRIAL OCCUPANCIES. IT SHALL BE THE |
| RESPONSIBILITY OF THE OWNER, AGENT, |
| PROPIETOR OR OCCUPANT OF GROUP S AND |
| GROUP F OCCUPANCIES, OR ANY OCCUPANCY |
| WHERE EXCESSIVE FLOOR LOADING IS LIKELY |
| TO OCCUR, TO EMPLOY A COMPETENT ARCHI- |
| TECT OR ENGINEER IN COMPUTING THE SAFE |
| FLOOR LOAD CAPACITY. ALL SUCH COMPUTA- |
| TIONS SHALL BE ACCOMPANIED BY AN AFFA- |
| DAVIT FROM THE ARCHITECT OR ENGINEER |
| STATING THE SAFE ALLOWABLE FLOOR LOADS |
| ON EACH FLOOR IN POUNDS PER SQ FT.THE |
| COMPUTATIONS & AFFADAVIT SHALL BE FILED |
| AS A PERMANENT RECORD OF THE BLDG DEPT. |
| |
| 7)106.4.3.SIGNS REQUIRED. IN EVERY |
| BUILDING OR PART OF A BUILDING USED FOR |
| STORAGE, INDUSTRIAL OR HAZARDOUS PUR- |
| POSES, THE SAFE FLOOR LOADS, AS REVIEWED |
| BY THE BUILDING OFFICIAL ON THE PLAN, |
| SHALL BE MARKED ON PLATES OF APPROVED DE |
| SIGN WHICH SHALL BE SUPPLIED & SECURELY |
| AFFIXED BY THE OWNER OF THE BUILDING IN |
| A CONSPICUOUS PLACE IN EACH STORY TO |
| WHICH THEY RELATE. SUCH PLATES SHALL NOT |
| BE REMOVEDOR DEFACED, & IF LOST, |
| REMOVED THE OWNER OF THE BUILDING SHALL |
| REPLACE THEM. |
| |
| 7) MEZZANINE NO GUARDRAILS? |
| |
| 8)1203.4.2 EVERY TOLIET ROOM SHALL |
| HAVE WINDOWS AS SPECIFIED FOR HABITABLE |
| ROOMS PROVIDING IN NO CASE LESS THAN 3 |
| SQ FT OPEN SPACE, OR HAVE APPROVED EQUIV |
| ALENT VENTILATION. |
| |
| 9) FL BLD CODE 1804.2.2 QUESTIONABLE |
| SOILS, WHERE THE BEARING CAPACITY IS |
| NOT DEFINETLY KNOWN OR IS IN QUESTION. |
| FOUNDATION NOTE(4) |
| |
| 10) DESIGN LOADS MISSING MEZZANINE: |
| TABLE 1604.1:LIGHT: 125 |
| HEAVY: 250 |
| |
| 11)106.4.2 STORAGE & FACTORY- INDUS- |
| TRIAL OCCUPANCIES. IT SHALL BE THE |
| RESPONSIBILITY OF THE OWNER, AGENT, |
| PROPIETOR OR OCCUPANT OF GROUP S AND |
| GROUP F OCCUPANCIES, OR ANY OCCUPANCY |
| WHERE EXCESSIVE FLOOR LOADING IS LIKELY |
| TO OCCUR, TO EMPLOY A COMPETENT ARCHI- |
| TECT OR ENGINEER IN COMPUTING THE SAFE |
| FLOOR LOAD CAPACITY. ALL SUCH COMPUTA- |
| TIONS SHALL BE ACCOMPANIED BY AN AFFA- |
| DAVIT FROM THE ARCHITECT OR ENGINEER |
| STATING THE SAFE ALLOWABLE FLOOR LOADS |
| ON EACH FLOOR IN POUNDS PER SQ FT.THE |
| COMPUTATIONS & AFFADAVIT SHALL BE FILED |
| AS A PERMANENT RECORD OF THE BLDG DEPT. |
| |
| 12)106.4.3.SIGNS REQUIRED. IN EVERY |
| BUILDING OR PART OF A BUILDING USED FOR |
| STORAGE, INDUSTRIAL OR HAZARDOUS PUR- |
| POSES, THE SAFE FLOOR LOADS, AS REVIEWED |
| BY THE BUILDING OFFICIAL ON THE PLAN, |
| SHALL BE MARKED ON PLATES OF APPROVED DE |
| SIGN WHICH SHALL BE SUPPLIED & SECURELY |
| AFFIXED BY THE OWNER OF THE BUILDING IN |
| A CONSPICUOUS PLACE IN EACH STORY TO |
| WHICH THEY RELATE. SUCH PLATES SHALL NOT |
| BE REMOVEDOR DEFACED, & IF LOST, |
| REMOVED THE OWNER OF THE BUILDING SHALL |
| REPLACE THEM. |
| |
| 13) PRECAST WALL SYSTEMS, MISSING INFO |
| ON PRECAST COLUMNS, WALL ATTACHMENT? |
| |
| BEFORE A PERMIT TO CONSTRUCT CAN BE |
| ISSUED, IMPACT FEES MUST BE PAID TO PALM |
| BEACH CO.,THE PERMIT PLANS STAMPED BY |
| THEM AND THE RECEIPT ATTACHED TO THE |
| PERMIT APPLICATION. |
| |
| LOOK FOR COMMENTS BY THE OTHER PLAN |
| REVIEW DISCIPLINES THAT MAY BE WRITTEN |
| ON THE APPLICATION, PLANS, OR ATTACHED |
| SEPARATELY. WHEN RESUBMITTING PLANS |
| PLEASE CLEARLY INDICATE THE REVISION AND |
| REMOVE AND REPLACE ANY PAGES AS NECESS- |
| ARY. A TRANSMITTAL LETTER LISTING THE |
| ORIGINAL REVIEW COMMENT NUMBER, WITH A |
| DESCRIPTION OF THE REVISION MADE, IDEN- |
| TIFYING THE SHEET OR SPECIFICATION PAGE |
| WHERE THE CHANGES CAN BE FOUND, WILL |
| HELP TO EXPEDITE YOUR PERMIT. THANK YOU |
| FOR YOUR ANTICIPATED COOPERATION. |