2002-06-18 00:00:00*************** UNSAT ******************
  
 1)NOTE: PLEASE LIST THE REQ`D ARC FAULT
 PROTECTED BRANCH CIRCUIT ON PANEL
 SCHEDULE. PLEASE NOTE THAT ALL PREVIOUS
 PLANS ARE COMING IN AND SHOWING AS
 "ACI" PROTECTED OUTLETS. PLEASE NOTE
 THAT THE PROTECTION REQ`D IS FOR THE
 ENTIRE BRANCH CIRCUIT. PLEASE ALSO NOTE
 THAT IT IS "AFCI" NOT "ACI" 210-12.
 THEY DO NOT MAKE AN "AFCI" RECEPT.
  
 2)NOTE: PLEASE NOTE THAT THE RISER
 DIAGRAM DOES NOT CORRELATE WITH ITSELF
 AND PANEL SCHEDULES? PLEASE NOTE,RISER
 NOTE SAYS, TO BE A 225A MCB AND RISER
 SHOWS 200A? PANEL ALSO SHOWN AS 200A.
 PLEASE CORRELATE.
  
 3)NOTE: PLEASE NOTE LOAD SHOWN FOR PANEL
 "B" EXCEEDS 60A FEED FOR THAT PANEL.
  
 4)NOTE: PLEASE NOTE PANEL "B" IS SHOWN
 AS 75A MLO? PLEASE NOTE THAT A 75A PANEL
 IS NOT A COMMON PANEL SIZE.?
  
 5)NOTE: PLEASE NOTE THAT ALL CODES REF
 THE "2001" NEC. PLEASE NOTE WE ARE UNDER
 THE "99" NEC.
  
 6)NOTE: PLEASE NOTE GFI RECEPT SPACING
 FOR MASTER BATH PER 210-52D. PLEASE NOTE
 GFI WITHIN 3' OF SINK.,
  
 7)NOTE: PLEASE CLARIFY OUTLET SPACING
 NEXT TO FRIG? COUNTER? 210-52(C)-1.
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE CALL.
  