Plan Review Notes For Permit 02061029 |
Permit Number |
02061029 |
|
Review Stop |
E |
Sequence Number |
2 |
|
Notes |
Date |
Text |
2002-09-16 00:00:00 | UNSAT | | ~~~~~ | | ~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~ | | | | PLEASE PROVIDE INFORMATION,MAKE | | NECESSARY CHANGES ON THE PLANS AND | | RESUBMIT FOR REVIEW. | | | | 1} THE RISER DIAGRAM SHOWS THE 2 1/2" | | CONDUIT LOOPING BETWEEN PANELS WITH | | 3-3/0'S BETWEEN THEM,PLEASE CLARIFY. | | | | 2} PLEASE INDICATE THE LOCATION OF THE | | SEOND ELECTRICAL PANEL ON THE PLAN. | | | | 3} CIRCUIT #3 IN PANEL "B" SHOULD BE ON | | A 20 AMP BREAKER TO COMPLY WITH | | 210-52(B) IF THAT CIRCUIT IS FOR THE | | DINING ROOM RECEPTACLES. | | | | 4} SHEET 7 ONLY SHOWS 2 CONDENSING UNITS | | ON THE DRAWING BUT LISTS THREE ON THE | | PANEL SCHEDULE. | | | | 5} PANEL "B" LISTS THREE AHU'S,THE LOAD | | CALCULATION LISTS TWO, PLEASE CLARIFY. | | | | 6} PLEASE NOTE THAT ALL PLANS | | DRAWN BY AN ARCHITECT/ENGINEER CONTAIN- | | ING A TITLE BLOCK, MUST BE SIGNED, | | DATED AND SEALED BY THE ARCH/ENGINEER OF | | RECORD. PER FS/FAC 481.221 & 471.025 | | | | IF THERE ARE ANY QUESTIONS PLEASE CALL; | | | | BILL TROBAUGH | | ELECTRICAL PLAN REVIEW | | 561/659-8096 EXT. 8392 |
|