2002-07-30 00:00:00CHECKLIST:
 1-NEED RECORDED NOTICE OF COMMENCEMENT.
 2-PERCENTAGE OF OPENINGS AT DINING ROOM
 EXCEEDS THE PERCENTAGE ALLOWED BY
 TABLE 600 FBC 2001.
 3-STRUCTURAL DRAWINGS SHALL HAVE ALL 5
 ITEMS REQUIRED BY SEC. 1606.1.7 FBC
 4-PROVIDE COMPLETE SECTION/DETAIL THRU
 FIREPLACE AND CHIMNEY. SEC. 104.2.1.2
 CITY AMENDMENTS TO FBC 2001.
 5-PROVIDE COMPLETE BEAM & LINTEL SCHED.
 & CLEARLY IDENTIFY THEM ON PLANS.
 SEC. 104.2.1.2 CITY AMENDMENTS TO FBC.
 6-PROVIDE COMPLETE DETAILS/ SECTIONS AND
 SPECS AT FRAMING FOR SLIDING GLASS
 DOORS @ LEISURE RM, INCLUDING CORNER.
 **NOTE: TAKE INTO CONSIDERATION THE SIZE
 OF DOORS AND PRODUCT APPROVAL FOR THIS
 TYPE OF INSTALLATION, INCLUDING CORNER
 UNION BETWEEN THE TWO ASSEMBLIES. ALSO
 HURRICANE MISSILE IMPACT PROTECTION.
 7-CLEARLY INDICATE ON PLANS MASONRY WALL
 VERTICAL REINFORCEMENT. SPACING IS NOT
 CLEAR. WHY THERE IS NOT REINFORCEMENT
 AT THE ENDS OF ALL OPENINGS/. HOW ARE
 THE OPENINGS REINFORCED TO RECEIVE THE
 HURRICANE MISSILE IMPACT ASSEMBLIES?
 **WHY THERE'S ONLY ONE SHEAR BLOCK WALL
 ON ENTIRE HOUSE?
 SEC. 104.2.1.2 CITY AMENDMENTS TO FBC.
 8-ENGINEER TO INCLUDE HIS LICENSE # AND
 TELEPHONE # ON ALL DRAWINGS AS REQ'D
 BY CHAPTER 471 FL STATUTES WHEN
 SUBMITTING PLANS FOR PUBLIC RECORDS.
 9-PROVIDE AREA TABULATION BREAKDOWN TO
 ASSESS VALUE AND RADON FEES. LIST A/C
 AREAS, PORCHES, GARAGE ETC.
 10-WHERE ARE PAGES 1 AND 2 OF THE SET OF
 DRAWINGS?.
 11-PROVIDE CURRENT DADE COUNTY OR SBCCI
 PRODUCT APPROVAL FOR:
 A)12' HIGH FIXED WINDOWS AS SHOWN ON
 PLANS. ALONG WITH CORRESPONDING VERT.
 MULLION. (MISSILE IMPACT)
 B)10' HIGH SLIDING GLASS DOORS AS SHOWN
 ON PLANS.
 C)10' HIGH SLIDING GLASS DOORS WITH
 SIDE POCKET ASSEMBLY AS SHOWN ON PLANS
 D)ACTUAL DADE COUNTY OR SBCCI PRODUCT
 EVALUATION FOR GARAGE DOOR.
 E)ROOF RIDGE VENTS.
 F)FIREPLACE UL LISTING AND SPECS.
 G)EXTERIOR SWING DOORS. EG. GARAGE, ETC.
 H)BBQ UL LISTING AND SPECS.
 I)SLIDING WINDOWS PRODUCT APPROVAL
 SUBMITTED REQUIRES STORM SHUTTERS FOR
 INSTALLATIONS BELOW 30'. SEE SHEET #2.
 CLARIFY IF PUTTING STORM SHUTTERS OR
 PROVIDE DIFFERENT PRODUCT APPROVAL.
 J)FRENCH DOORS WITH TRANSOM ABOVE SINGLE
 ASSEMBLY AS SHOWN ON PLANS. OR ENG'R
 TO PROVIDE HEADER SPECS & CONNECTORS &
 ATTACHMENT OF FRENCH DOOR AND TRANSOM
 FRAME TO SUCH MULLION TO CREATE A
 SINGLE UNIT.
 12-PROVIDE COMPLETE FRAMING DETAILS FOR
 ROUND AND ARCHED WINDOWS AT MASONRY
 WALL AND FRAMED WALL.
 SEC. 104.2.1.2 CITY AMENDMENTS TO FBC.
 13-ARCHITECTURAL DRAWINGS DON'T SPECIFY
 TYPE OF ROOF TO BE INSTALLED.
 14-PROVIDE UPLIFT CALCULATIONS AT LANAI
 COLUMN FOOTERS. SEC. 1606.1.3 FBC 2001
 15-CLEARLY KEY PLANS THAT PERTAIN TO
 THIS HOUSE. DELETE THE OTHERS.
 16-ENERGY CALCULATIONS:
 A)REVISE THE UNDER ATTIC AREA. SEE SEC.
 604.1.A.1 CHAPTER 13 FBC 2001.
 B)COMPLETE TOP OF FORM; ADDRESS, ETC.
 17-SEE PLANS FOR ADDITIONAL COMMENTS AND
 PLEASE, RETURN REVIEWED SET AFTER
 CORRECTIONS ARE DONE TO ORIGINAL DWGS
 TO EXPEDITE THE REVIEW PROCESS.