Date |
Text |
2002-07-30 00:00:00 | CHECKLIST: |
| 1-NEED RECORDED NOTICE OF COMMENCEMENT. |
| 2-PERCENTAGE OF OPENINGS AT DINING ROOM |
| EXCEEDS THE PERCENTAGE ALLOWED BY |
| TABLE 600 FBC 2001. |
| 3-STRUCTURAL DRAWINGS SHALL HAVE ALL 5 |
| ITEMS REQUIRED BY SEC. 1606.1.7 FBC |
| 4-PROVIDE COMPLETE SECTION/DETAIL THRU |
| FIREPLACE AND CHIMNEY. SEC. 104.2.1.2 |
| CITY AMENDMENTS TO FBC 2001. |
| 5-PROVIDE COMPLETE BEAM & LINTEL SCHED. |
| & CLEARLY IDENTIFY THEM ON PLANS. |
| SEC. 104.2.1.2 CITY AMENDMENTS TO FBC. |
| 6-PROVIDE COMPLETE DETAILS/ SECTIONS AND |
| SPECS AT FRAMING FOR SLIDING GLASS |
| DOORS @ LEISURE RM, INCLUDING CORNER. |
| **NOTE: TAKE INTO CONSIDERATION THE SIZE |
| OF DOORS AND PRODUCT APPROVAL FOR THIS |
| TYPE OF INSTALLATION, INCLUDING CORNER |
| UNION BETWEEN THE TWO ASSEMBLIES. ALSO |
| HURRICANE MISSILE IMPACT PROTECTION. |
| 7-CLEARLY INDICATE ON PLANS MASONRY WALL |
| VERTICAL REINFORCEMENT. SPACING IS NOT |
| CLEAR. WHY THERE IS NOT REINFORCEMENT |
| AT THE ENDS OF ALL OPENINGS/. HOW ARE |
| THE OPENINGS REINFORCED TO RECEIVE THE |
| HURRICANE MISSILE IMPACT ASSEMBLIES? |
| **WHY THERE'S ONLY ONE SHEAR BLOCK WALL |
| ON ENTIRE HOUSE? |
| SEC. 104.2.1.2 CITY AMENDMENTS TO FBC. |
| 8-ENGINEER TO INCLUDE HIS LICENSE # AND |
| TELEPHONE # ON ALL DRAWINGS AS REQ'D |
| BY CHAPTER 471 FL STATUTES WHEN |
| SUBMITTING PLANS FOR PUBLIC RECORDS. |
| 9-PROVIDE AREA TABULATION BREAKDOWN TO |
| ASSESS VALUE AND RADON FEES. LIST A/C |
| AREAS, PORCHES, GARAGE ETC. |
| 10-WHERE ARE PAGES 1 AND 2 OF THE SET OF |
| DRAWINGS?. |
| 11-PROVIDE CURRENT DADE COUNTY OR SBCCI |
| PRODUCT APPROVAL FOR: |
| A)12' HIGH FIXED WINDOWS AS SHOWN ON |
| PLANS. ALONG WITH CORRESPONDING VERT. |
| MULLION. (MISSILE IMPACT) |
| B)10' HIGH SLIDING GLASS DOORS AS SHOWN |
| ON PLANS. |
| C)10' HIGH SLIDING GLASS DOORS WITH |
| SIDE POCKET ASSEMBLY AS SHOWN ON PLANS |
| D)ACTUAL DADE COUNTY OR SBCCI PRODUCT |
| EVALUATION FOR GARAGE DOOR. |
| E)ROOF RIDGE VENTS. |
| F)FIREPLACE UL LISTING AND SPECS. |
| G)EXTERIOR SWING DOORS. EG. GARAGE, ETC. |
| H)BBQ UL LISTING AND SPECS. |
| I)SLIDING WINDOWS PRODUCT APPROVAL |
| SUBMITTED REQUIRES STORM SHUTTERS FOR |
| INSTALLATIONS BELOW 30'. SEE SHEET #2. |
| CLARIFY IF PUTTING STORM SHUTTERS OR |
| PROVIDE DIFFERENT PRODUCT APPROVAL. |
| J)FRENCH DOORS WITH TRANSOM ABOVE SINGLE |
| ASSEMBLY AS SHOWN ON PLANS. OR ENG'R |
| TO PROVIDE HEADER SPECS & CONNECTORS & |
| ATTACHMENT OF FRENCH DOOR AND TRANSOM |
| FRAME TO SUCH MULLION TO CREATE A |
| SINGLE UNIT. |
| 12-PROVIDE COMPLETE FRAMING DETAILS FOR |
| ROUND AND ARCHED WINDOWS AT MASONRY |
| WALL AND FRAMED WALL. |
| SEC. 104.2.1.2 CITY AMENDMENTS TO FBC. |
| 13-ARCHITECTURAL DRAWINGS DON'T SPECIFY |
| TYPE OF ROOF TO BE INSTALLED. |
| 14-PROVIDE UPLIFT CALCULATIONS AT LANAI |
| COLUMN FOOTERS. SEC. 1606.1.3 FBC 2001 |
| 15-CLEARLY KEY PLANS THAT PERTAIN TO |
| THIS HOUSE. DELETE THE OTHERS. |
| 16-ENERGY CALCULATIONS: |
| A)REVISE THE UNDER ATTIC AREA. SEE SEC. |
| 604.1.A.1 CHAPTER 13 FBC 2001. |
| B)COMPLETE TOP OF FORM; ADDRESS, ETC. |
| 17-SEE PLANS FOR ADDITIONAL COMMENTS AND |
| PLEASE, RETURN REVIEWED SET AFTER |
| CORRECTIONS ARE DONE TO ORIGINAL DWGS |
| TO EXPEDITE THE REVIEW PROCESS. |