Plan Review Notes
Plan Review Notes For Permit 02061029
Permit Number 02061029
Review Stop E
Sequence Number 1
Notes
Date Text
2002-07-02 00:00:00UNSAT
 ~~~~~
 ~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~
 PLEASE PROVIDE THE FOLLOWING
 INFORMATION,MAKE ANY NECESSARY CHANGES
 ON THE DRAWING AND RESUBMIT FOR REVIEW.
  
 1} PLEASE SUBMIT AIC RATINGS FOR
 ALL NEW EQUIPMENT BEING INSTALLED.
 MAINS/PANELS/BREAKERS MUST BE RATED FOR
 THE AVAILABLE FAULT CURRENT PER 110-9.
  
 2} PLEASE SUBMIT LOAD CALCAULATION
 -S.PER 220,215-5.
  
 3} SUBMIT A RISER DIAGRAM INDICATING ALL
 SERVICE EQUIPMENT AMPERAGE
 RATINGS,RISER CONDUIT & WIRE SIZES AND
 GROUNDING SYSTEM USED WITH GEC SIZE.
  
 4} PLEASE SHOW GARAGE RECEPTACLES PER
 210-8 ON PLANS.
  
 5} SHOW SERVICE EQUIPMENT LOCATION ON
 PLANS.
  
 6} PLEASE SHOW ALL A/C EQUIPMENT
 LOCATIONS ON ELECTRICAL
 DRAWINGS,AHU'S,CONDENSERS AND
 DISCONNECTS.
  
 7} PLEASE LIST THE REQ'D ARC
 FAULT PROTECTED CIRCUITS ON PANEL
 SCHEDULE. PER 210-12
  
 8} PLEASE LIST THE REQ'D BATH(S)
 CIRCUIT(S). PER 210-11-C-3
 MUST BE 20A AND #12AWG.
  
 9} PLEASE NOTE KITCHEN COUNTER-
 SPACE RECEPTACLES TO BE GFI PER
 210-8(A)(6). NOTE SAME ON PLANS.
  
 BILL TROBAUGH
 ELECTRICAL PLAN REVIEW
 561/659-8096 EXT. 8392