Plan Review Notes For Permit 02061029 |
Permit Number |
02061029 |
|
Review Stop |
E |
Sequence Number |
1 |
|
Notes |
Date |
Text |
2002-07-02 00:00:00 | UNSAT | | ~~~~~ | | ~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~ | | PLEASE PROVIDE THE FOLLOWING | | INFORMATION,MAKE ANY NECESSARY CHANGES | | ON THE DRAWING AND RESUBMIT FOR REVIEW. | | | | 1} PLEASE SUBMIT AIC RATINGS FOR | | ALL NEW EQUIPMENT BEING INSTALLED. | | MAINS/PANELS/BREAKERS MUST BE RATED FOR | | THE AVAILABLE FAULT CURRENT PER 110-9. | | | | 2} PLEASE SUBMIT LOAD CALCAULATION | | -S.PER 220,215-5. | | | | 3} SUBMIT A RISER DIAGRAM INDICATING ALL | | SERVICE EQUIPMENT AMPERAGE | | RATINGS,RISER CONDUIT & WIRE SIZES AND | | GROUNDING SYSTEM USED WITH GEC SIZE. | | | | 4} PLEASE SHOW GARAGE RECEPTACLES PER | | 210-8 ON PLANS. | | | | 5} SHOW SERVICE EQUIPMENT LOCATION ON | | PLANS. | | | | 6} PLEASE SHOW ALL A/C EQUIPMENT | | LOCATIONS ON ELECTRICAL | | DRAWINGS,AHU'S,CONDENSERS AND | | DISCONNECTS. | | | | 7} PLEASE LIST THE REQ'D ARC | | FAULT PROTECTED CIRCUITS ON PANEL | | SCHEDULE. PER 210-12 | | | | 8} PLEASE LIST THE REQ'D BATH(S) | | CIRCUIT(S). PER 210-11-C-3 | | MUST BE 20A AND #12AWG. | | | | 9} PLEASE NOTE KITCHEN COUNTER- | | SPACE RECEPTACLES TO BE GFI PER | | 210-8(A)(6). NOTE SAME ON PLANS. | | | | BILL TROBAUGH | | ELECTRICAL PLAN REVIEW | | 561/659-8096 EXT. 8392 |
|