2002-07-30 00:00:00************ UNSAT *********************
  
 1)NOTE: PLEASE CLARIFY MEANS OF DISC
 ON GENERATOR. PLEASE NOTE MEANS OF DISC
 MUST BE LOCATED ON THE EXTERIOR IF
 WHEN OPENED EXPOSING LIVE PARTS.445-6
 PLEASE ALSO NOTE THAT SINCE GENERATOR
 IS LOCATED CLOSE TO MAIN ELECTRICAL
 ROOM, SIGNAGE REQ`D PER 230-2-E
 PLEASE NOTE THAT A SHUNT TRIP IS NOT
 RATED FOR A MEANS OF DISC. PLEASE SEE
 230-76,230-79.
  
 2)NOTE: PLEASE ALSO NOTE THAT ALL OLD
 SHEETS NEED TO BE TAKEN OUT OF PLANS
 AND HAVE NEW SHEETS INSERTED.
  
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW.IF THERE ARE ANY QUESTIONS,
 PLEASE CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 561-659-8096 EXT 8372