Plan Review Notes For Permit 02061002 |
Permit Number |
02061002 |
|
Review Stop |
E |
Sequence Number |
2 |
|
Notes |
Date |
Text |
2002-07-30 00:00:00 | ************ UNSAT ********************* | | | | 1)NOTE: PLEASE CLARIFY MEANS OF DISC | | ON GENERATOR. PLEASE NOTE MEANS OF DISC | | MUST BE LOCATED ON THE EXTERIOR IF | | WHEN OPENED EXPOSING LIVE PARTS.445-6 | | PLEASE ALSO NOTE THAT SINCE GENERATOR | | IS LOCATED CLOSE TO MAIN ELECTRICAL | | ROOM, SIGNAGE REQ`D PER 230-2-E | | PLEASE NOTE THAT A SHUNT TRIP IS NOT | | RATED FOR A MEANS OF DISC. PLEASE SEE | | 230-76,230-79. | | | | 2)NOTE: PLEASE ALSO NOTE THAT ALL OLD | | SHEETS NEED TO BE TAKEN OUT OF PLANS | | AND HAVE NEW SHEETS INSERTED. | | | | | | PLEASE SUBMIT THE ABOVE INFORMATION FOR | | REVIEW.IF THERE ARE ANY QUESTIONS, | | PLEASE CALL. | | | | DEWEY PALMER | | ELECTRICAL PLAN REVIEW | | 561-659-8096 EXT 8372 |
|