2002-07-15 00:00:00 | |
| BUILDING PLAN REVIEW |
| PERMIT: 02061002 |
| ADD: 321 15TH STREET |
| CONT: CATALFUMO CONSTRUCTION |
| TEL: (561) 694-3000 |
| FL BLD CODE= 2001 FLORIDA BUILDING CODE |
| |
| 1)FL BLD CODE 104.2.1.2 |
| ADDITIONAL INFORMATION REQUIRED, |
| SHEET A-3 DETAIL P-3 INDICATES THE TOP |
| ENCLOSURE BY R. F. SHEILDING CONTRACTOR, |
| WHAT SHIELDING IS TO BE COMPLETED? HOW |
| IS IT TO BE SUPPORTED? FROM THE BOTTOM |
| CORD OF BAR JOIST? HAS THE ENGINEER OF |
| RECORD APPROVED THE ADDITIONAL WEIGTH |
| BEING HUNG FROM BAR JOIST? |
| |
| 2)704.2.1.4 CORRIDOR PARTITIONS, SMOKE |
| STOP PARTITIONS, HORIZONTAL EXIT PART- |
| ITIONS, EXIT ENCLOSURES, AND FIRE |
| RATED WALLS REQUIRED TO HAVE PROTECTED |
| OPENINGS SHALL BE EFFECTIVELY AND |
| PERMANETLY IDENTIFIED WITH SIGNS OR |
| STENCILING IN A MANNER ACCEPTABLE TO THE |
| AUTHORITY HAVING JURISDICTION. SUCH IDEN |
| TIFICATION SHALL BE ABOVE ANY DECORATIVE |
| CEILING CEILING AND IN CONCEALED SPACES. |
| SUGGESTED WORDING" FIRE & SMOKE BARRIER |
| PROTECT ALL OPENINGS". |
| |
| 3)11-4.13.6 MANEUVERING CLEARENCES |
| AT DOORS. MINIMUM MANEUVERING CLEARENCES |
| AT DOORS THAT ARE NOT AUTOMATIC OR |
| POWER-ASSISTED SHALL BE AS SHOWN IN |
| FIG. 25. THE FLOOR OR GROUND AREA WITH |
| IN THE REQUIRED CLEARENCES SHALL BE |
| CLEAR & LEVEL. |
| |
| 4)11-4.22.2 DOORS. ALL DOORS TO |
| ACCESSIBLE TOLIET ROOMS SHALL COMPLY |
| WITH 11-4.13. DOORS SHALL NOT SWING INTO |
| CLEAR FLOOR SPACE REQUIRED FOR ANY |
| FIXTURE. |
| |
| TABLE 803.3 MINIMUM INTERIOR FINISH |
| CLASSIFICATION; PROVIDE INFORMATION |
| BASED ON INTERIOR FINISH REQUIREMENTS |
| BASED ON OCCUPANCY |
| |
| LOOK FOR COMMENTS BY THE OTHER PLAN |
| REVIEW DISCIPLINES THAT MAY BE WRITTEN |
| ON THE APPLICATION, PLANS, OR ATTACHED |
| SEPARATELY. WHEN RESUBMITTING PLANS |
| PLEASE CLEARLY INDICATE THE REVISION AND |
| REMOVE AND REPLACE ANY PAGES AS NECESS- |
| ARY. A TRANSMITTAL LETTER LISTING THE |
| ORIGINAL REVIEW COMMENT NUMBER, WITH A |
| DESCRIPTION OF THE REVISION MADE, IDEN- |
| TIFYING THE SHEET OR SPECIFICATION PAGE |
| WHERE THE CHANGES CAN BE FOUND, WILL |
| HELP TO EXPEDITE YOUR PERMIT. THANK YOU |
| FOR YOUR ANTICIPATED COOPERATION. |
| JIM WITMER |
| PLAN REVIEW |
| TEL: (561)659-8096 EX.8412 |
| FAX: (561)659-8026 |