2002-08-01 00:00:00 | BUILDING DENIED |
| |
| 1) STRUCTURE IS LOCATED IN AN "AO" FLOOD |
| ZONE AN ELEVATION CERTIFICATE WILL BE |
| REQUIRED. |
| |
| 2)FL BLDG 1909.3 (EXCEPTION# 2) |
| CONCRETE SLABS ON GRADE CONTAINING 6X6/ |
| W1.4XW1.4 WELDED WIRE REINFORCEMENT |
| FABRIC LOCATED IN THE MIDDLE TO THE |
| UPPER 1/3RD OF THE SLAB SHALL BE SUP- |
| PORTED BY APPROVED MATERIALS OR SUPPORTS |
| AT SPACING NOT TO EXCEED 3 FT OR IN |
| ACCORDANCE WITH MANUFACTURER'S SPEC. |
| PLEASE INDICATE ON PLANS. |
| |
| 3)1707.4.5.2 MULLIONS SHALL BE DESIGN- |
| ED TO TRANSFER THE DESIGN PRESSURE LOADS |
| APPLIED BY THE WINDOW OR DOOR ASSEMBLIES |
| TO THE ROUGH OPENING SUBTRATE. PLEASE |
| PROVIDE PRODUCT APPROVAL FOR CLIPPED |
| MULLIONS. |
| |
| 4)2305.2.2 FLOOR/CEILING ASSEMBLIES |
| SINGLE FAMILY DWELLINGS. IN FLOOR/CEIL/ |
| ING ASSEMBLIES SEPARATING USEABLE SPACE |
| INTO 2 OR MORE APPROXIMATE AREAS WITH NO |
| AREA GREATER THAN 500 SQ FT. DRAFTSTOP- |
| PING SHALL BE PROVIDED PARALLEL TO THE |
| MAIN FRAMING MEMBERS. PLEASE INDICATE |
| ON PLANS THE LOCATION AND MATERIALS THAT |
| WILL BE USED. |
| |
| 5) PROVIDE CLARIFICATION OF CANTILEVER |
| BEAMS. THE PLANS DO NOT INDICATE WHERE |
| THE WALL ON THE RIGHT SIDE OF THE |
| COVERED PORCH ENDS AND THE CANT. BEAM |
| BEGINS. THE FOUNDATION, WALL AND |
| VERTICAL REINFORCEMENT ON SHEETS 1,2 & |
| 3B FOR THE RIGHT WALL AT THE COVERED |
| PORCH DOES NOT MATCH THE ELEVATIONS. |
| |
| 6) THE POSITIVE WINDLOAD PRESSURE LISTED |
| ON THE PLANS FOR THE GARAGE DOOR (+39.8) |
| EXCEEDS THE POS. DESIGN PRESSURE GIVEN |
| IN THE PRODUCT APPROVAL FOR THE OVERHEAD |
| GARAGE DOOR. PLEASE SUBMIT AN ACCEPTABLE |
| PRODUCT APPROVAL. |
| |
| 7) PLEASE UPDATE THE PRODUCT APPROVAL |
| COVER SHEET (WIND PRESSURE SCHEDULE) |
| THAT LISTS THE WINDOWS AND DOORS AND |
| THEIR PRODUCT ACCEPTANCE NUMBERS. |
| |
| 8)1707.4.5.2 MULLIONS SHALL BE DESIGN- |
| ED TO TRANSFER THE DESIGN PRESSURE LOADS |
| APPLIED BY THE WINDOW OR DOOR ASSEMBLIES |
| TO THE ROUGH OPENING SUBTRATE. |
| PLEASE SUBMIT PRODUCT APPROVALS FOR |
| CLIPPED MULLIONS. |
| |
| 9) THE KEY PLANS AND INSTALLATION |
| SCHEDULES SUBMITTED FOR THE STORM PANELS |
| ARE FOR THE WRONG MODEL. |
| |
| ROBERT MCDOUGAL |
| BLDG. PLAN REVIEW |
| (561)659-8096 EXT.8202 |