Plan Review Notes
Plan Review Notes For Permit 02060891
Permit Number 02060891
Review Stop FIRE
Sequence Number 1
Notes
Date Text
2002-06-18 00:00:001) PLANS INDICATE THAT DUCT SMOKE
 DETECTORS WILL BE CAUSE A TROUBLE
 SIGNAL WHICH IS NOT ACCEPTABLE.
 ACTIVATION OF THE DUCT SMOKE DETECTORS
 ARE TO CAUSE THE FIRE ALARM SYSTEM TO
 ACTIVATE.
  
 MIKE CARSILLO, ASSISTANT FIRE MARSHAL
 659-8096,EXT.8497
 835-2910