2002-06-25 00:00:00 | PROVISO:MECHANICAL PERMIT 02060906 |
| |
| 2001 FBC(M) 402.2 - NATURAL VENTILATION |
| FOR OUTSIDE AIR REQUIRMENT. SHOW |
| COMPLIANCE FOR THE MINIMUM OPENABLE AREA |
| TO THE OUTDOORS. (4 PERCENT OF THE FLOOR |
| AREA BEING VENTILATED) OR TABLE 403.3 |
| FOR MECHANICAL VENTILATION. |
| |
| SMOKE DETECTORS SHALL BE INSTALLED |
| SUPPLY SYSTEMS WITH A DESIGN CAPACITY |
| GREATER THAN 2,000 CFM, IN THE SUPPLY |
| AIR DUCT. 2001 FBC(M) 606.2.1OR |
| UPON ACTIVATION, THE SMOKE DETECTORS |
| SHALL SHUTDOWN THE AIR DISTRIBUTION |
| SYSTEM. 2001 FBC(M) 606.4 |
| |
| SHOULD A GAS DRYER BE INSTALLED - |
| SHOW COMPLIANCE FOR COMBUSTION AIR AS |
| PER 2001 FBC(M) CHAPTER 7. |
| |
| CONDENSATE SHALL DISCHARGE A MINIMUM OF |
| 12" AWAY FROM THE BUILDING STRUCTURE AS |
| PER 2001 FBC 1503.4.4. |
| |
| AHU LOCATED IN GARAGE - |
| APPLIANCES SHALL NOT BE INSTALLED IN A |
| LOCATION WHERE SUBJECT TO MECHANICAL |
| DAMAGE UNLESS PROTECTED BY APPROVED |
| BARRIERS.2001 FBC(M) 303.4 |
| |
| IF YOU HAVE ANY QUESTIONS, PLEASE |
| CONTACT PATTY KRAUSS AT 659-8096 |
| EXT. 8388. |