Plan Review Notes For Permit 02060778 |
Permit Number |
02060778 |
|
Review Stop |
FIRE |
Sequence Number |
1 |
|
Notes |
Date |
Text |
2002-07-16 00:00:00 | 1) DOOR SCHEDULE INDICATES THAT A | | SOLENOID WILL BE CONNECTED TO THE | | DOOR LATCH. ONLY DELAYED EGRESS OR | | ACCESS CONTROLLED EGRESS WILL BE | | ALLOWED ON REQUIRED EXIT DOORS. PLEASE | | SEE NFPA 101, 2000 EDITION, CHAPTER 7. | | | | 2) EXIT DOOR LOCKS SHALL NOT REQUIRE | | THE USE OF ANY KEYS, TOOLS, OR | | SPECIAL KNOWLEDGE TO OPERATE. | | | | MIKE CARSILLO, ASSISTANT FIRE MARSHAL | | 659-8096,EXT.8497 | | 835-2910 |
|