2002-06-19 00:00:00*******************DENIED***************
  
 MECHANICAL PERMIT 02060811
  
 REFERENCE BEDROOM 1 & 2 -
 BALANCED RETURN AIR - 2001 FBC(M) 601.4
 RETURN AIR SHALL BE EQUAL TO SUPPLY
 AIR BY MEANS OF AIR TRANSFER OR A RETURN
 AIR (JUMPER).
  
 SUPPLY AIR SYSTEMS WITH THE DESIGN
 CAPACITY OR COMBINED DESIGNED CAPACITY
 GREATER THAN 2,000 CFM SHALL HAVE FAN
 SHUTDOWN IN ACCORDANCE WITH THE
 FOLLOWING - DUCT SMOKE DETECTOR OR UPON
 ACTIVATION, THE SMOKE DETECTORS SHALL
 SHUT DOWN THE AIR DISTRIBUTION SYSTEM.
 2001 FBC(M) 606.2.1 OR 606.4.
  
 IF YOU HAVE ANY QUESTIONS, PLEASE
 CONTACT PATTY KRAUSS AT 659-8096
 EXT. 8388.