2002-07-17 00:00:00 | BUILDING DENIED |
| |
| 1) A RECORDED COPY OF THE NOTICE OF |
| COMMENCEMENT MUST BE SUBMITTED BEFORE A |
| PERMIT CAN BE ISSUED. |
| |
| 2) IMPACT FEES MUST BE PAID TO PALM |
| BEACH COUNTY, PLANS STAMPED BY THEM AND |
| COPY OF RECEIPT SUBMITTED TO CITY OF |
| WEST PALM BEACH BUILDING DEPARTMENT, |
| BEFORE A BUILDING PERMIT CAN BE ISSUED. |
| |
| 3)FL BLDG 1909.3 (EXEPTION# 2) |
| CONCRETE SLABS ON GRADE CONTAINING 6X6/ |
| W1.4XW1.4 WELDED WIRE REINFORCEMENT |
| FABRIC LOCATED IN THE MIDDLE TO THE |
| UPPER 1/3RD OF THE SLAB SHALL BE SUP- |
| PORTED BY APPROVED MATERIALS OR SUPPORTS |
| AT SPACING NOT TO EXCEED 3 FT OR IN |
| ACCORDANCE WITH MANUFACTURER'S SPEC. |
| PLEASE INDICATE ON PLANS. |
| |
| 4) PROVIDE DETAILS FOR THE STEEL COLUMN |
| CAPS AND BASES ON PLANS. INDICATE THE |
| SIZE,THICKNESS,WELD TYPE,LOCATION AND |
| SIZE OF BOLT HOLES,ETC. |
| |
| 5) INDICATE THE COMPONENT & CLADDING |
| WIND PRESSURES FOR THE ROOF COVERING. |
| |
| 6) THE GLASS BLOCK IN BATHS 2,3 & 4 ARE |
| IN HAZARDOUS LOCATIONS WHICH REQUIRE |
| TEMPERED GLASS OR GLASS BLOCK WITH A |
| MINIMUM FACE UNIFORM FACE THICKNESS OF |
| 0.25". FBC 2405.2.1 & 2404.2.2. |
| |
| 7) THE MAIN EGRESS DOOR (FRONT DOOR) IS |
| REQUIRED TO HAVE A MINIMUM CLEAR OPENING |
| OF 32".(EACH LEAF OF A DOUBLE DOOR MUST |
| COMPLY) FBC 1012.1 |
| |
| 8) INDICATE THE OPENING SIZE OF THE |
| ATTIC ACCESS ON THE PLANS. |
| |
| 9) THE CANTILEVERED CONCRETE BEAM DETAIL |
| ON SHEET 6 CALLS FOR THE TOP STEEL TO |
| RUN 36" BEYOND THE EDGE OF THE OPENING, |
| HOWEVER, THE COLUMNS ARE ONLY 2'WIDE. |
| PLEASE PROVIDE STEEL PLACEMENT DETAIL |
| FOR THE CANT. BEAM. |
| |
| 10)THE LINTELS FOR THE OPENINGS ADJACENT |
| TO THE CANTILEVER BEAM REQUIRE A MINIMUM |
| END BEARING OF 4". PLEASE INDICATE HOW |
| THIS WILL BE ACCOMPLISHED AT THE COLUMNS |
| FOR THE CANT. BEAM. |
| |
| 11) THE ROOF FRAMING PLAN ON SHEET 6 |
| DOES NOT CLEARLY INDICATE THE TRUSS |
| LAYOUT. THE ANCHORS ARE NOT INDICATED |
| FOR ALL OF THE TRUSS BEARING POINTS. THE |
| WOOD GIRDERS TO CONC. FILLED BLOCK |
| COLUMNS ANCHORS ARE NOT INDICATED ON THE |
| PLANS. THE BEAM HEIGHT INDICATED AT THE |
| GARAGE DOES NOT AGREE WITH THE BEAM |
| HEIGHT LEGEND. |
| |
| 12) THE GLASS BLOCK DETAIL ON SHEET 8 |
| REFERENCES THE S.F.B.C. PLEASE REVISE TO |
| 2001 FBC. |
| |
| 13) THE SOIL REPORT STATES THAT EXTERIOR |
| FOUNDATIONS SHOULD BEAR AT LEAST 18" |
| BELOW ADJACENT OUTSIDE FINAL GRADES. THE |
| CITY AMENDMENTS TO THE FBC 1804.1.7 |
| REQUIRE MONOLITHIC FOUNDATIONS AT |
| HABITABLE AREAS TO BE A MINIMUM OF 4" |
| ABOVE FINISH GRADE. THIS WILL REQUIRE A |
| 22" DEEP FOUNDATION AND THE PLANS |
| INDICATE 16" DEEP FOOTINGS. PLEASE |
| CORRECT. |
| |
| 14) PLEASE CORRECT THE ATTACHMENT/ |
| FASTENER SPECIFICATIONS ON SHEET 8 FOR |
| WIRE LATH. REFER TO ASTM C 1063 FOR THE |
| ATTACHMENT OF METAL LATH WHICH VARIES BY |
| TYPE, 710.2.2 FOR FLAT RIB AND 7.10.2.3 |
| FOR 3/8" RIB LATH. FBC 2504.2.2. |
| |
| 15) THE PRODUCT APPROVALS FOR PREMDOR |
| HAVE DRAWINGS WHICH DO NOT MATCH THE |
| REPORT. THE ACCEPTANCE NOS. DIFFER. ALSO |
| THE DESIGN PRESSURES ARE NOT LISTED. |
| THE DRAWINGS FOR THE PREMDOOR ENTERGY |
| BRAND DOOR IS MISSING THE REPORT. |
| |
| 16) THE SITE SPECIFIC PRODUCT APPROVALS |
| FOR THE NORANDEX MULLIONS REQUIRE THE |
| EMBOSSED SEAL AND SIGNATURE OF THE |
| ENGINEER THAT IS CERTIFYING THE PRODUCT |
| IN ADDITION THAT OF THE DESIGNER OF |
| RECORD. |
| |
| 17)PROVIDE ENGINEERING FOR BUTT GLASS |
| ASSEMBLY. WHERE OTHER THAN FIRM SUPPORT |
| ON ALL SIDES IS PROVIDED, DETAILED SHOP |
| DRAWINGS, SPECIFICATIONS AND RATIONAL |
| ANALYSIS AND/OR TEST DATA ASSURING SAFE |
| PERFORMANCE FOR THE SPECIFIC APPLICATION |
| SHALL BE PREPARED BY ENGINEERS |
| EXPERIENCED IN THIS WORK. FBC 2406.2 |
| |
| 18) PROVIDE (2) CURRENT AND COMPLETE |
| COPIES OF SBCCI OR METRO-DADE PRODUCT |
| APPROVALS FOR: |
| - GLASS BLOCK |
| |
| 19)PROVIDE (2) PRODUCT APPROVALS, KEY |
| PLANS AND INSTALLATION SCHEDULES |
| INDICATING THE SPECIFIC TYPE OF |
| FASTENER AND MOUNTING OPTIONS THAT WILL |
| BE USED (CIRCLE OR HIGHLIGHT THESE ON |
| THE PRODUCT APPROVAL DRAWINGS). THIS |
| INFORMATION IS REQUIRED AT TIME OF |
| PERMIT OR A SEPARATE PERMIT WILL BE |
| REQUIRED WITH ADDITIONAL PERMIT FEES. |
| |