2002-06-25 00:00:00PROVISO:MECHANICAL PERMIT 02060865
 UNIT - BL
  
 2001 FBC(M) 402.2 - NATURAL VENTILATION
 FOR OUTSIDE AIR REQUIRMENT. SHOW
 COMPLIANCE FOR THE MINIMUM OPENABLE AREA
 TO THE OUTDOORS. (4 PERCENT OF THE FLOOR
 AREA BEING VENTILATED) OR TABLE 403.3
 FOR MECHANICAL VENTILATION.
  
 CONDENSATE SHALL DISCHARGE A MINIMUM OF
 12" AWAY FROM THE BUILDING STRUCTURE AS
 PER 2001 FBC 1503.4.4.
  
 APPLIANCES SHALL NOT BE INSTALLED IN A
 LOCATION WHERE SUBJECT TO MECHANICAL
 DAMAGE UNLESS PROTECTED BY APPROVED
 BARRIERS.2001 FBC(M) 303.4
  
 OVERFLOW PROTECTION REQUIRED AS PER
 2001 FBC(M) 307.2.3.
  
 THE MAXIMUM DEVELOPED LENGTH FOR THE
 DRYER VENT SHALL NOT EXCEED 25 FT WITH
 A 5 FT REDUCTION FOR EACH 90 DEGREE
 BEND & A 2 1/2 REDUCTION FOR EACH 45
 DEGREE BEND.
  