Plan Review Notes For Permit 02060679 |
Permit Number |
02060679 |
|
Review Stop |
M |
Sequence Number |
1 |
|
Notes |
Date |
Text |
2002-06-25 00:00:00 | PROVISO:MECHANICAL PERMIT 02060865 | | UNIT - BL | | | | 2001 FBC(M) 402.2 - NATURAL VENTILATION | | FOR OUTSIDE AIR REQUIRMENT. SHOW | | COMPLIANCE FOR THE MINIMUM OPENABLE AREA | | TO THE OUTDOORS. (4 PERCENT OF THE FLOOR | | AREA BEING VENTILATED) OR TABLE 403.3 | | FOR MECHANICAL VENTILATION. | | | | CONDENSATE SHALL DISCHARGE A MINIMUM OF | | 12" AWAY FROM THE BUILDING STRUCTURE AS | | PER 2001 FBC 1503.4.4. | | | | APPLIANCES SHALL NOT BE INSTALLED IN A | | LOCATION WHERE SUBJECT TO MECHANICAL | | DAMAGE UNLESS PROTECTED BY APPROVED | | BARRIERS.2001 FBC(M) 303.4 | | | | OVERFLOW PROTECTION REQUIRED AS PER | | 2001 FBC(M) 307.2.3. | | | | THE MAXIMUM DEVELOPED LENGTH FOR THE | | DRYER VENT SHALL NOT EXCEED 25 FT WITH | | A 5 FT REDUCTION FOR EACH 90 DEGREE | | BEND & A 2 1/2 REDUCTION FOR EACH 45 | | DEGREE BEND. | | | | IF YOU HAVE ANY QUESTIONS, PLEASE | | CONTACT PATTY KRAUSS AT 659-8096 | | EXT. 8388. |
|