2002-07-09 00:00:00BUILDING DENIED
  
 1) A RECORDED COPY OF THE NOTICE OF
 COMMENCEMENT MUST BE SUBMITTED BEFORE A
 PERMIT CAN BE ISSUED.
  
 2) THE STRUCTURE IS LOCATED IN AN 'A8'
 FLOOD ZONE, AN ELEVATION CERTIFICATE IS
 REQUIRED.
  
 3) PROVIDE A SOIL BEARING REPORT PER THE
 CITY OF WPB AMENDMENTS TO THE 2001 FBC
 SEC. 1804.2.2.
  
 4) INDICATE THE APPLICABLE INTERNAL
 PRESSURE COEFFICIENT AND THE BASIC WIND
 PRESSURE ON THE PLANS AS REQUIRED BY THE
 FBC SEC. 1606.1.7.
  
 5) PLEASE CORRECT #1 UNDER FOUNDATION
 NOTES ON C-1 TO 0.006 POLYETHELENE
 (6 MIL) AS REQUIRED BY THE 2001 FBC SEC.
 1909.2.
  
 6) THE WINDOW (H) IN THE FIRST FLOOR
 BATHROOM IS REQUIRED TO HAVE SAFETY
 GLAZING PER 2405.2.1.
  
 7) PLEASE CHANGE NOTE 6 UNDER GENERAL
 NOTES ON A-2 TO REFERENCE THE 2001
 FLORIDA PLUMBING CODE.
  
 8) THE NAIL SIZE AND SPACING GIVEN FOR
 THE SECOND STORY FLOOR DIAPHRAM AT
 SECTION 2 ON SHEET S-2 DOES NOT AGREE
 WITH THE FLOOR DIAPHRAM INFORMATION
 LISTED IN THE SCHEDULE.
  
 9) THE A/C AREA LISTED ON THE PLANS
 DIFFERS FROM THE CONDITIONED AREA LISTED
 ON THE ENERGY CALCULATIONS. PLEASE
 CORRECT.
  
 10) THE ENERGY FORM LISTS 180 SQ.FT. OF
 ADJACENT WOOD FRAME WALLS,HOWEVER,THERE
 ARE NONE SHOWN ON THE PLAN. PLEASE
 REVISE ENERGY FORMS.
  
 11) FIREBLOCKING IS REQUIRED AT THE TOP
 OF THE STAIR RUN BY FBC 2305.1.4. PLEASE
 INDICATE THE LOCATION AND MATERIAL THAT
 WILL BE USED FOR THIS ON THE PLANS.
  
 12) INDICATE THE LOCATIONS AND MATERIALS
 USED FOR THE REQUIRED DRAFTSTOPPING OF
 THE FLOOR/CEILING ASSEMBLY.
  
 13) PROVIDE (2) CURRENT AND COMPLETE
 COPIES OF SBCCI OR METRO-DADE PRODUCT
 APPROVALS FOR:
 - FRONT DOUBLE DOOR WITHOUT SIDELITES
 - STRUCTURAL MULLIONS
 - SINGLE HUNG WINDOWS (THE COVER PAGE OF
 THOSE SUBMITTED HAS A DIFFERENT
 ACCEPTANCE NUMBER THAN THE OTHER PAGES)
  
 14) PROVIDE AN INSTALLATION SCHEDULE FOR
 THE STORM PANELS. INDICATE THE TYPE OF
 FASTENER AND MOUNTING OPTION THAT WILL
 BE USED (CIRCLE OR HIGHLIGHT THESE ON
 THE PRODUCT APPROVAL DRAWINGS). THIS
 INFORMATION IS REQUIRED AT THE TIME OF
 PERMIT OR A SEPARATE PERMIT WILL BE
 REQUIRED FOR THE STORM PANELS WITH
 ADDITIONAL FEES.
  