2002-07-09 00:00:00 | BUILDING DENIED |
| |
| 1) A RECORDED COPY OF THE NOTICE OF |
| COMMENCEMENT MUST BE SUBMITTED BEFORE A |
| PERMIT CAN BE ISSUED. |
| |
| 2) THE STRUCTURE IS LOCATED IN AN 'A8' |
| FLOOD ZONE, AN ELEVATION CERTIFICATE IS |
| REQUIRED. |
| |
| 3) PROVIDE A SOIL BEARING REPORT PER THE |
| CITY OF WPB AMENDMENTS TO THE 2001 FBC |
| SEC. 1804.2.2. |
| |
| 4) INDICATE THE APPLICABLE INTERNAL |
| PRESSURE COEFFICIENT AND THE BASIC WIND |
| PRESSURE ON THE PLANS AS REQUIRED BY THE |
| FBC SEC. 1606.1.7. |
| |
| 5) PLEASE CORRECT #1 UNDER FOUNDATION |
| NOTES ON C-1 TO 0.006 POLYETHELENE |
| (6 MIL) AS REQUIRED BY THE 2001 FBC SEC. |
| 1909.2. |
| |
| 6) THE WINDOW (H) IN THE FIRST FLOOR |
| BATHROOM IS REQUIRED TO HAVE SAFETY |
| GLAZING PER 2405.2.1. |
| |
| 7) PLEASE CHANGE NOTE 6 UNDER GENERAL |
| NOTES ON A-2 TO REFERENCE THE 2001 |
| FLORIDA PLUMBING CODE. |
| |
| 8) THE NAIL SIZE AND SPACING GIVEN FOR |
| THE SECOND STORY FLOOR DIAPHRAM AT |
| SECTION 2 ON SHEET S-2 DOES NOT AGREE |
| WITH THE FLOOR DIAPHRAM INFORMATION |
| LISTED IN THE SCHEDULE. |
| |
| 9) THE A/C AREA LISTED ON THE PLANS |
| DIFFERS FROM THE CONDITIONED AREA LISTED |
| ON THE ENERGY CALCULATIONS. PLEASE |
| CORRECT. |
| |
| 10) THE ENERGY FORM LISTS 180 SQ.FT. OF |
| ADJACENT WOOD FRAME WALLS,HOWEVER,THERE |
| ARE NONE SHOWN ON THE PLAN. PLEASE |
| REVISE ENERGY FORMS. |
| |
| 11) FIREBLOCKING IS REQUIRED AT THE TOP |
| OF THE STAIR RUN BY FBC 2305.1.4. PLEASE |
| INDICATE THE LOCATION AND MATERIAL THAT |
| WILL BE USED FOR THIS ON THE PLANS. |
| |
| 12) INDICATE THE LOCATIONS AND MATERIALS |
| USED FOR THE REQUIRED DRAFTSTOPPING OF |
| THE FLOOR/CEILING ASSEMBLY. |
| |
| 13) PROVIDE (2) CURRENT AND COMPLETE |
| COPIES OF SBCCI OR METRO-DADE PRODUCT |
| APPROVALS FOR: |
| - FRONT DOUBLE DOOR WITHOUT SIDELITES |
| - STRUCTURAL MULLIONS |
| - SINGLE HUNG WINDOWS (THE COVER PAGE OF |
| THOSE SUBMITTED HAS A DIFFERENT |
| ACCEPTANCE NUMBER THAN THE OTHER PAGES) |
| |
| 14) PROVIDE AN INSTALLATION SCHEDULE FOR |
| THE STORM PANELS. INDICATE THE TYPE OF |
| FASTENER AND MOUNTING OPTION THAT WILL |
| BE USED (CIRCLE OR HIGHLIGHT THESE ON |
| THE PRODUCT APPROVAL DRAWINGS). THIS |
| INFORMATION IS REQUIRED AT THE TIME OF |
| PERMIT OR A SEPARATE PERMIT WILL BE |
| REQUIRED FOR THE STORM PANELS WITH |
| ADDITIONAL FEES. |
| |
| ROBERT MCDOUGAL |
| BLDG. PLAN REVIEW |
| (561)659-8096 EXT.8202 |