Plan Review Notes For Permit 02060563 |
Permit Number |
02060563 |
|
Review Stop |
R |
Sequence Number |
2 |
|
Notes |
Date |
Text |
2002-11-07 00:00:00 | BUILDING REVIEW APPROVED WITH PROVISO: | | 1-STORM SHUTTERS: | | A)DESIGN PRESSURES SPECIFIED HAVE LIMI- | | TATIONS ON PANEL SPAN. SEE DESIGN | | PRESSURES CALCULATED BY THE ARCHITECT | | AND REVISE SCHEDULE AS REQUIRED. ALSO, | | CLARIFY ANCHOR USED. | | B)MARK ON DRAWINGS SPECIFIC MOUNTING | | CONDITIONS AND ANCHOR TYPE & SPACING | | TO BE USED. | | 2-SPECIFY SIZE OF ANCHOR BOLT AND WASHER | | FOR GARAGE STRUCTURAL BUCK DETAIL. | | SEC. 104.2.1.2 CITY AMENDMENTS TO FBC. | | 3-DETAIL 5/S3 IS MISSING THE CONNECTOR | | TYPE AND SPACING. TRUSS ANCHOR SCHE- | | DULE DOESN'T SPECIFY ANY CONNECTOR AT | | THIS GABLE END AREA. | | 4-ROOF SHEATHING & NAILING STATEMENT AND | | DIAPHRAGM SCHEDULE DON'T MATCH. REVISE | | AS REQUIRED. ALSO, REVISE SECTIONS/ | | DETAILS TO MATCH AS WELL. |
|