2002-07-09 00:00:00 | CHECKLIST: |
| 1-NEED RECORDED NOTICE OF COMMENCEMENT. |
| 2-ENTRY DOORS DON'T PROVIDE THE 32" MIN. |
| CLEAR OPENING REQUIRED BY TABLE 1004 |
| 3-ENERGY CALCULATIONS: A)WRONG MODEL. |
| B)THERE ARE NOT ADJACENT FRAMED WALLS. |
| C)OWNER/AGENT TO DATE BOTTOM OF FORM TOO |
| 4-WINDOW BY ENTRY PORCH EXCEEDS THE MAX. |
| PERCENTAGE OF OPENINGS ALLOWED BY |
| TABLE 600 FBC 2001. REVISE AS REQUIRED |
| 5-SURVEY IS MISSING SOME SETBACK |
| DIMENSIONS (SEE SIDE SETBACKS). |
| 6-SPECIFY FIREBLOCKING MATERIAL AND |
| LOCATION AT STAIRS. SEC. 2305 FBC 2001 |
| **NOTE: FIREBLOCKING & DRAFSTOPPING ARE |
| 2 DIFFERENT THINGS. |
| 7-SPECIFY FIRECUT AT MASONRY WALL AS |
| REQUIRED BY SEC. 2305.4 FBC 2001. |
| 8-SPECIFY ON 2ND FL. FRAMING PLAN THE |
| LOCATION & MATERIAL FOR DRAFSTOPPING |
| AS REQUIRED BY SEC. 2305.2.2 FBC 2001. |
| 9-PROVIDE SOIL TEST REPORT. |
| 10-STORM SHUTTERS: |
| A)PROVIDE COMPLETE INSTALLATION SCHEDULE |
| AND KEY PLAN. SEE CITY SAMPLE. |
| B)CLEARLY INDICATE ON DRAWINGS SPECIFIC |
| MOUNTING CONDITIONS AND ANCHOR TYPE & |
| SPACING TO BE USED ACCORDING TO THE |
| MEAN ROOF HEIGHT, DESIGN PRESSURES, |
| EDGE DISTANCE, PANEL SPAN, CONNECTION |
| TYPE & STRUCTURE TO BE ATTACHED TO |
| (CONCRETE BLOCK OR CONCRETE). |
| |
| 11-PROVIDE PRODUCT APPROVAL FOR: |
| A)ENTRY DOORS AS SHOWN ON PLANS. |
| B)COMPLETE PANAMERICAN WINDOW MULLION |
| PRODUCT APPROVAL. |
| C)SINGLE HUNG WINDOWS PRODUCT APPROVAL |
| REPORT DOESN'T MATCH DRAWINGS. |
| D)GARAGE SIDE SWING DOOR. |
| 12-PROVIDE UPDATED ORIGINAL LETTER FOR |
| MASONRY UNITS USED ADDRESSED TO CITY |
| OF W.P.B AND THE CONTRACTOR. AND |
| SPECIFY PROJECT. |
| 13-SHEET C-1 IS MISSING THE INTERNAL |
| PRESSURE COEFFICIENT AS REQUIRED BY |
| SEC. 1606.1.7 FBC 2001. |
| 14-PROVIDE COMPLETE GABLE END WALL |
| DETAILS FOR GABLE ENDS SHOWN AT FRONT |
| ELEVATION. SEE SEC. 2117 FBC 2001. |
| 15-SEE PLANS FOR COMMENTS. |