2002-07-03 00:00:00 | BUILDING DENIED |
| |
| 1)A RECORDED COPY OF THE NOTICE OF |
| COMMENCEMENT MUST BE SUBMITTED BEFORE A |
| PERMIT CAN BE ISSUED. |
| |
| 2) STRUCTURE IS LOCATED IN AN "A8" FLOOD |
| ZONE AN ELEVATION CERTIFICATE WILL BE |
| REQUIRED. |
| |
| 3) PROVIDE A SOIL BEARING REPORT PER |
| CITY AMENDMENTS TO THE 2001 FBC 1804.2.2 |
| |
| 4) INDICATE THE APPLICABLE INTERNAL |
| PRESSURE COEFFICIENT ON THE PLANS AS |
| REQUIRED BY FBC 1606.1.7. |
| |
| 5) THE SQUARE FOOTAGE GIVEN ON THE PLANS |
| FOR THE GARAGE ON SHEET C-1 IS 557 SQFT. |
| AND ON A-1 IS 427SQFT. PLEASE CLARIFY. |
| |
| 6) THE BONUS ROOM IS REQUIRED TO BE |
| PERMANETLY MARK ON THE PLANS THAT IT IS |
| NOT TO BE USED FOR SLEEPING PURPOSES. |
| OPENINGS FROM A GARAGE DIRECTLY INTO A |
| ROOM USED FOR SLEEPING IS NOT PERMITTED |
| PER FBC 411.2.8. |
| |
| 7) THE WINDOW (H) IN THE FIRST FLOOR |
| BATH ROOM IS REQUIRED TO HAVE TEMPERED |
| GLASS, BECAUSE IT IS WITHIN 3 FEET |
| HORIZONALLY OF THE TUB PER FBC 2405.2.1. |
| |
| 8) PLEASE CHANGE NOTE 6 UNDER GENERAL |
| NOTES ON SHEET A-2 TO REFERENCE THE |
| 2001 FLORIDA PLUMBING CODE. |
| |
| 9) SECTION B ON A-6 INDICATES R-19 |
| INSULATION IN THE ATTIC AND THE ENERGY |
| CALCULATIONS LISTS R-30. PLEASE CORRECT. |
| |
| 10) THE NAILS AND SPACING LISTED FOR THE |
| FLOOR ON SECTION 2 ON SHEET S-2 DOES NOT |
| CORRESPOND WITH THE FLOOR DIAPHRAGM |
| NAILING SPECIFIED IN THE SCHEDULE. |
| |
| 11) THE CONDITIONED FLOOR AREA LISTED ON |
| THE ENERGY CALCULATIONS DIFFERS FROM THE |
| A/C AREA GIVEN ON THE PLANS. PLEASE |
| CORRECT. |
| |
| 12) INDICATE ON THE PLANS THAT THE BONUS |
| ROOM WALLS ARE INSULATED. |
| |
| 13) THE AREA UNDER ATTIC LISTED ON THE |
| ENERGY CALCS. DOES NOT APPEAR TO INCLUDE |
| THE BONUS ROOM. THE ADJACENT WOOD FRAME |
| WALL AREA DOES NOT APPEAR TO BE CORRECT. |
| PLEASE REVIEW AND CORRECT. |
| |
| 14) PROVIDE (2) CURRENT AND COMPLETE |
| COPIES OF SBCCI OR METRO-DADE PRODUCT |
| APPROVALS FOR: |
| - FRONT DOOR (OUTSWING DOUBLE DOORS |
| WITHOUT SIDELITES) |
| - STRUCTURAL MULLIONS (THE ONES THAT |
| WERE SUBMITTED EXPIRED ON 5-30-02) |
| |
| 16) PROVIDE AN INSTALLATION SCHEDULE FOR |
| THE STORM PANELS. INDICATE THE TYPE OF |
| FASTENER AND MOUNTING OPTIONS THAT WILL |
| BE USED (CIRCLE OR HIGHLIGHT ON THE |
| PRODUCT APPROVAL DRAWINGS). THIS |
| INFORMATION IS REQUIRED AT TIME OF |
| PERMIT OR A SEPARATE PERMIT WILL BE |
| REQUIRED WITH ADDITIONAL PERMIT FEES. |
| |
| IF YOU HAVE ANY QUESTIONS PLEASE CALL: |
| ROBERT MCDOUGAL |
| BLDG. PLAN REVIEW |
| (561)659-8096 EXT.8202 |