Plan Review Notes
Plan Review Notes For Permit 02060560
Permit Number 02060560
Review Stop R
Sequence Number 1
Notes
Date Text
2002-07-03 00:00:00BUILDING DENIED
  
 1)A RECORDED COPY OF THE NOTICE OF
 COMMENCEMENT MUST BE SUBMITTED BEFORE A
 PERMIT CAN BE ISSUED.
  
 2) STRUCTURE IS LOCATED IN AN "A8" FLOOD
 ZONE AN ELEVATION CERTIFICATE WILL BE
 REQUIRED.
  
 3) PROVIDE A SOIL BEARING REPORT PER
 CITY AMENDMENTS TO THE 2001 FBC 1804.2.2
  
 4) INDICATE THE APPLICABLE INTERNAL
 PRESSURE COEFFICIENT ON THE PLANS AS
 REQUIRED BY FBC 1606.1.7.
  
 5) THE SQUARE FOOTAGE GIVEN ON THE PLANS
 FOR THE GARAGE ON SHEET C-1 IS 557 SQFT.
 AND ON A-1 IS 427SQFT. PLEASE CLARIFY.
  
 6) THE BONUS ROOM IS REQUIRED TO BE
 PERMANETLY MARK ON THE PLANS THAT IT IS
 NOT TO BE USED FOR SLEEPING PURPOSES.
 OPENINGS FROM A GARAGE DIRECTLY INTO A
 ROOM USED FOR SLEEPING IS NOT PERMITTED
 PER FBC 411.2.8.
  
 7) THE WINDOW (H) IN THE FIRST FLOOR
 BATH ROOM IS REQUIRED TO HAVE TEMPERED
 GLASS, BECAUSE IT IS WITHIN 3 FEET
 HORIZONALLY OF THE TUB PER FBC 2405.2.1.
  
 8) PLEASE CHANGE NOTE 6 UNDER GENERAL
 NOTES ON SHEET A-2 TO REFERENCE THE
 2001 FLORIDA PLUMBING CODE.
  
 9) SECTION B ON A-6 INDICATES R-19
 INSULATION IN THE ATTIC AND THE ENERGY
 CALCULATIONS LISTS R-30. PLEASE CORRECT.
  
 10) THE NAILS AND SPACING LISTED FOR THE
 FLOOR ON SECTION 2 ON SHEET S-2 DOES NOT
 CORRESPOND WITH THE FLOOR DIAPHRAGM
 NAILING SPECIFIED IN THE SCHEDULE.
  
 11) THE CONDITIONED FLOOR AREA LISTED ON
 THE ENERGY CALCULATIONS DIFFERS FROM THE
 A/C AREA GIVEN ON THE PLANS. PLEASE
 CORRECT.
  
 12) INDICATE ON THE PLANS THAT THE BONUS
 ROOM WALLS ARE INSULATED.
  
 13) THE AREA UNDER ATTIC LISTED ON THE
 ENERGY CALCS. DOES NOT APPEAR TO INCLUDE
 THE BONUS ROOM. THE ADJACENT WOOD FRAME
 WALL AREA DOES NOT APPEAR TO BE CORRECT.
 PLEASE REVIEW AND CORRECT.
  
 14) PROVIDE (2) CURRENT AND COMPLETE
 COPIES OF SBCCI OR METRO-DADE PRODUCT
 APPROVALS FOR:
 - FRONT DOOR (OUTSWING DOUBLE DOORS
 WITHOUT SIDELITES)
 - STRUCTURAL MULLIONS (THE ONES THAT
 WERE SUBMITTED EXPIRED ON 5-30-02)
  
 16) PROVIDE AN INSTALLATION SCHEDULE FOR
 THE STORM PANELS. INDICATE THE TYPE OF
 FASTENER AND MOUNTING OPTIONS THAT WILL
 BE USED (CIRCLE OR HIGHLIGHT ON THE
 PRODUCT APPROVAL DRAWINGS). THIS
 INFORMATION IS REQUIRED AT TIME OF
 PERMIT OR A SEPARATE PERMIT WILL BE
 REQUIRED WITH ADDITIONAL PERMIT FEES.
  
 IF YOU HAVE ANY QUESTIONS PLEASE CALL:
 ROBERT MCDOUGAL
 BLDG. PLAN REVIEW
 (561)659-8096 EXT.8202