Plan Review Notes For Permit 02060560 |
Permit Number |
02060560 |
|
Review Stop |
M |
Sequence Number |
1 |
|
Notes |
Date |
Text |
2002-06-17 00:00:00 | *******************DENIED*************** | | | | MECHANICAL PERMIT 02060617 | | | | AIR CONDITIONING SCHEDULE ON PLAN SHEET | | MP-2 DO NOT MATCH THE ENERGY CALCS OR | | CFM DISTRIBUTION AS INDICATED ON THE | | PLAN.PLEASE CORRECT AIR CONDITIONING | | SCHEDULE (2-AHU #1 ARE LISTED AT 1200 | | CFM) | | | | PROVISO: | | CONDENSATE SHALL DISCHARGE A MINIMUM OF | | 12" AWAY FROM THE BUILDING STRUCTURE AS | | PER 2001 FBC 1503.4.4. | | | | OVERFLOW PROTECTION REQUIRED AS PER | | 2001 FBC(M) 307.2.3. | | | | IF YOU HAVE ANY QUESTIONS, PLEASE | | CONTACT PATTY KRAUSS AT 659-8096 | | EXT. 8388. |
|