2002-08-13 00:00:00CHECKLIST:
 1-PROVIDE ENGINEERING ANALYSIS & CALCS.
 CLARIFY HOW ARE WIND LOADS BEING
 TRANSFERED TO THE FLOOR AND CEILING
 DIAPHRAGMS. SEE SECTIONS 1606.2.4,
 2105 AND 2107 FBC 2001.
 2-NEED RECORDED NOTICE OF COMMENCEMENT.
 3-SEE COMMENTS ON PLANS. PLEASE RETURN
 REVIEWED SET AFTER CORRECTIONS ARE
 DONE TO EXPEDITE REVIEW PROCESS.
 4-SPECIFY FIRECUTS ON STRUCTURAL DWGS
 ALSO. SEC. 2305.1.4 FBC 2001.
 5-PROVIDE SOIL TEST REPORT.
 6-PROVIDE COMPLETE INFORMATION FOR STORM
 SHUTTERS. NEED KEY PLAN, INSTALLATION
 SCHEDULE AND PRODUCT APPROVAL WITH
 MATCHING LEGIBLE DRAWINGS.
 7-PROVIDE PRODUCT APPROVAL:
 A)ENTRY DOORS WITH LEGIBLE DRAWINGS.
 B)ARCHED WINDOWS WITH LEGIBLE DRAWINGS
 THAT MATCH THE PRODUCT APPROVAL.
 C)GLASS BLOCK COMPLETE UL SPECIFICATIONS
 FOR ONE HOUR FIRE RATED ASSEMBLY AS
 REQUIRED BY TABLE 600 FBC 2001.
 8-REVISE DETAIL FOR 2X STRUCTURAL BUCK
 REQUIRED BY THE PRODUCT APPROVAL. SEE
 DETAIL SUBMITTED & DETAIL FOR FRAMING
 @ ARCHED OPENINGS. THEY DON'T MATCH.
 9-SPECIFY FIREBLOCKING SIZE AND LOCATION
 AT STAIRS, INCLUDING AT TOP OF STAIRS.
 SEC. 2305.1.4 FBC 2001.
 10-REVISE CONNECTORS SPECIFIED AT TOP OF
 FRAMING WALLS. CONNECTOR SPECIFIED IS
 DESIGNED TO BE EMBEDED INTO CONCRETE.
 NEED WOOD TO WOOD CONNECTOR.
 11-PROVIDE COMPLETE DETAILS & SPECS FOR
 CONSTRUCTION AND INSTALLATION OF WOOD
 FRAMED SHEAR WALL. SEE SEC. 2313 FBC.
 SPECIFY ALL FASTENERS AT THE ENDS AND
 CORNERS. AT FRAMING OF OPENINGS, ETC.