2002-07-06 00:00:00 | CHECKLIST: |
| 1-NEED RECORDED NOTICE OF COMMENCEMENT. |
| 2-REVISE ATTIC SIZE. 36"MIN. SEC 2309.6 |
| 3-CLARIFY SIZE OF EGRESS WINDOWS. 24SH |
| AND 34SH WINDOWS DON'T MEET THE MIN. |
| CLEAR HEIGHT & CLEAR OPENING REQUIRED |
| BY SEC. 1005.4.4 FBC 2001. ARE THESE |
| CUSTOM MADE WINDOWS? |
| 4-SPECIFY FIREBLOCKING MATERIAL AND |
| LOCATION AT STAIRS. SEC. 2305 FBC. |
| NOTE: FIREBLOCKING AND DRAFTSTOPPING |
| ARE TWO DIFFERENT THINGS. |
| 5-SPECIFY FIRECUT AT MASONRY WALL AS |
| REQUIRED BY SEC. 2305.4 FBC 2001. |
| 6-PROVIDE SOIL TEST REPORT. |
| 7-STORM SHUTTERS: |
| A)PROVIDE COMPLETE INSTALLATION SCHEDULE |
| AND KEY PLAN. SEE CITY SAMPLE. |
| B)CLEARLY INDICATE ON DRAWINGS SPECIFIC |
| MOUNTING CONDITIONS & ANCHOR TYPE AND |
| SPACING TO BE USED ACCORDING TO THE |
| MEAN ROOF HEIGHT, DESIGN PRESSURES, |
| EDGE DISTANCE, PANEL SPAN, CONNECTION |
| TYPE AND STRUCTURE TO BE ATTACHED TO |
| (CONCRETE BLOCK OR CONCRETE, OR WOOD) |
| 8-PROVIDE PRODUCT APPROVAL FOR: |
| A)SINGLE ENTRY DOOR A SHOWN ON PLANS. |
| B)COMPLETE PAN AMERICAN WINDOW MULLION |
| PRODUCT APPROVAL. |
| C)ARCHED WINDOW NEED LEGIBLE DRAWINGS. |
| D)SINGLE HUNG PRODUCT APPROVAL REPORT |
| DOESN'T MATCH DRAWINGS SUBMITTED. |
| E)ONE HR FIRE RATED GLASS BLOCK ASSEMBLY |
| 9-PROVIDE UPDATED ORIGINAL LETTER FOR |
| MASONRY USED ADDRESSED TO THE CITY OF |
| W.P.B. AND THE CONTRACTOR AND SPECIFY |
| THE PROJECT WHERE IS GOING TO BE USED. |
| 10-SHEET C-1 IS MISSING THE INTERNAL |
| PRESSURE COEFFICIENT AS REQUIRED BY |
| SECTION 1606.1.7 FBC 2001. |
| 11-PROVIDE GABLE END DETAIL SHOWING |
| STRUCTURAL CONTINUITY AS REQUIRED ON |
| SECTION 2117 FBC 2001. |
| 12-REVISE GLASS BLOCK DETAIL. NEED 1 HR |
| FIRE RATED ASSEMBLY AS REQUIRED BY |
| TABLE 600 FBC 2001. SEE UL LISTING. |
| 13-MASTER BEDROOM TO HAVE DOOR WITH 29" |
| MIN. CLEAR OPENING. SEC. 11-11 FBC. |
| 14-PROVIDE ATTIC ACCESS ABOVE FRONT AREA |
| OF GARAGE. SEC. 2309.6 FBC 2001. |
| 15-SEE PLANS FOR ADDITIONAL COMMENTS AND |
| RETURN REVIEWED SET TO EXPEDITE REVIEW |
| 16-SPECIFY SUPPORTS FOR CONCRETE SLAB |
| WWM. SEE SEC. 1909.3 FBC 2001. |
| 17-CONNECTOR SPECIFIED FOR FRONT FRAMED |
| WALL ARE FOR WOOD TO CONCRETE, NOT FOR |
| WOOD TO WOOD APPLICATION. REVISE AS |
| REQUIRED. SEE SHEET S-1 FOR COMMENTS. |