2002-07-06 00:00:00CHECKLIST:
 1-NEED RECORDED NOTICE OF COMMENCEMENT.
 2-REVISE ATTIC SIZE. 36"MIN. SEC 2309.6
 3-CLARIFY SIZE OF EGRESS WINDOWS. 24SH
 AND 34SH WINDOWS DON'T MEET THE MIN.
 CLEAR HEIGHT & CLEAR OPENING REQUIRED
 BY SEC. 1005.4.4 FBC 2001. ARE THESE
 CUSTOM MADE WINDOWS?
 4-SPECIFY FIREBLOCKING MATERIAL AND
 LOCATION AT STAIRS. SEC. 2305 FBC.
 NOTE: FIREBLOCKING AND DRAFTSTOPPING
 ARE TWO DIFFERENT THINGS.
 5-SPECIFY FIRECUT AT MASONRY WALL AS
 REQUIRED BY SEC. 2305.4 FBC 2001.
 6-PROVIDE SOIL TEST REPORT.
 7-STORM SHUTTERS:
 A)PROVIDE COMPLETE INSTALLATION SCHEDULE
 AND KEY PLAN. SEE CITY SAMPLE.
 B)CLEARLY INDICATE ON DRAWINGS SPECIFIC
 MOUNTING CONDITIONS & ANCHOR TYPE AND
 SPACING TO BE USED ACCORDING TO THE
 MEAN ROOF HEIGHT, DESIGN PRESSURES,
 EDGE DISTANCE, PANEL SPAN, CONNECTION
 TYPE AND STRUCTURE TO BE ATTACHED TO
 (CONCRETE BLOCK OR CONCRETE, OR WOOD)
 8-PROVIDE PRODUCT APPROVAL FOR:
 A)SINGLE ENTRY DOOR A SHOWN ON PLANS.
 B)COMPLETE PAN AMERICAN WINDOW MULLION
 PRODUCT APPROVAL.
 C)ARCHED WINDOW NEED LEGIBLE DRAWINGS.
 D)SINGLE HUNG PRODUCT APPROVAL REPORT
 DOESN'T MATCH DRAWINGS SUBMITTED.
 E)ONE HR FIRE RATED GLASS BLOCK ASSEMBLY
 9-PROVIDE UPDATED ORIGINAL LETTER FOR
 MASONRY USED ADDRESSED TO THE CITY OF
 W.P.B. AND THE CONTRACTOR AND SPECIFY
 THE PROJECT WHERE IS GOING TO BE USED.
 10-SHEET C-1 IS MISSING THE INTERNAL
 PRESSURE COEFFICIENT AS REQUIRED BY
 SECTION 1606.1.7 FBC 2001.
 11-PROVIDE GABLE END DETAIL SHOWING
 STRUCTURAL CONTINUITY AS REQUIRED ON
 SECTION 2117 FBC 2001.
 12-REVISE GLASS BLOCK DETAIL. NEED 1 HR
 FIRE RATED ASSEMBLY AS REQUIRED BY
 TABLE 600 FBC 2001. SEE UL LISTING.
 13-MASTER BEDROOM TO HAVE DOOR WITH 29"
 MIN. CLEAR OPENING. SEC. 11-11 FBC.
 14-PROVIDE ATTIC ACCESS ABOVE FRONT AREA
 OF GARAGE. SEC. 2309.6 FBC 2001.
 15-SEE PLANS FOR ADDITIONAL COMMENTS AND
 RETURN REVIEWED SET TO EXPEDITE REVIEW
 16-SPECIFY SUPPORTS FOR CONCRETE SLAB
 WWM. SEE SEC. 1909.3 FBC 2001.
 17-CONNECTOR SPECIFIED FOR FRONT FRAMED
 WALL ARE FOR WOOD TO CONCRETE, NOT FOR
 WOOD TO WOOD APPLICATION. REVISE AS
 REQUIRED. SEE SHEET S-1 FOR COMMENTS.