Plan Review Notes
Plan Review Notes For Permit 02060558
Permit Number 02060558
Review Stop M
Sequence Number 1
Notes
Date Text
2002-06-18 00:00:00PROVISO:MECHANICAL PERMIT 02060622
  
 CONDENSATE SHALL DISCHARGE A MINIMUM OF
 12" AWAY FROM THE BUILDING STRUCTURE AS
 PER 2001 FBC 1503.4.4.
  
 2001 FBC(M) 402.2 - NATURAL VENTILATION
 FOR OUTSIDE AIR REQUIRMENT. SHOW
 COMPLIANCE FOR THE MINIMUM OPENABLE AREA
 TO THE OUTDOORS. (4 PERCENT OF THE FLOOR
 AREA BEING VENTILATED) OR TABLE 403.3
 FOR MECHANICAL VENTILATION.
  
 OVERFLOW PROTECTION REQUIRED AS PER
 2001 FBC(M) 307.2.3.
  
 PLEASE NOTE ON THE 2ND FLOOR BEDROOM 2
 CFM TO THIS AREA IS 1695?PLEASE
 CORRECT.
  