Plan Review Notes
Plan Review Notes For Permit 02060555
Permit Number 02060555
Review Stop R
Sequence Number 3
Notes
Date Text
2002-10-30 00:00:00SUBMITTAL CHECKLIST:
 1-PROVIDE SOIL TEST REPORT.
 2-STORM SHUTTERS: A)CLARIFY DESIGN PRE-
 SSURES. SEE ARCHITECTURAL DWGS. NOTE:
 DESIGN PRESSURES LIMITS THE MAX. SPAN
 OF PANELS. B)CLEARLY INDICATE ON DWGS
 ANCHOR TYPE AND SPACING TO BE USED IN
 THIS PROJECT. C)CLARIFY IF USING RAWL
 OR CAULK-IN ANCHORS. D)PROVIDE COMPLE-
 TE SBCCI PRODUCT APPROVAL REPORT.
 3-ARCHITECT TO CLARIFY DESIGN PRESSURES
 CALCULATED FOR ENTRY DOORS. SEE FLOOR
 PLAN AND EXTERIOR ELEVATION.
 4-PROVIDE COMPLETE INFORMATION FOR
 STRUCTURAL BUCK DETAIL AT GARAGE.
 MISSING ANCHOR BOLT SIZE AND WASHER.
 SEC. 104.2.1.2 CITY AMENDMENTS TO FBC.
 5-REVISED TRUSS ANCHOR SCHEDULE IS NOT
 CORRECT. SEE USP CATALOGUE FOR NAIL
 TYPE AND CORRESPONDING VALUES OR
 PROVIDE ENGINEERING CALCULATIONS FOR
 DIFFERENT VALUES.
 104.2.1.2 CITY AMENDMENTS TO FBC 2001.
 6-DETAIL 5/S3 IS NOT GOOD. CONNECTOR
 HL210 IS A PURLIN HANGER. IT DOESN'T
 RESIST THE CALCULATED LOADS AND IS NOT
 INTENDED TO SUPPORT BEAMS. SEE USP
 CATALOGUE AND 2ND FLOOR FRAMING PLAN.
 REVISE CONNECTION AS REQUIRED.
 7-SPECIFY ROOF TRUSS CONNECTOR @ GIRDER
 TRUSS WITH UPLIFT LOAD OF 2537#.
 8-REVISE CONNECTOR (2)TC-6 FOR THE OTHER
 ROOF GIRDER TRUSS. USE VALUES OF RE-
 REVISED TRUSS ANCHOR SCHEDULE. SEE USP
 CATALOGUE. SEC. 104.2.1.2 CITY AMENDM/