Plan Review Notes For Permit 02060555 |
Permit Number |
02060555 |
|
Review Stop |
R |
Sequence Number |
2 |
|
Notes |
Date |
Text |
2002-08-06 00:00:00 | APPROVED WITH PROVISO: | | 1-PROVIDE SIGNED AND SEALED SOIL TEST | | REPORT. | | 2-STORM SHUTTERS: | | A)DRAWINGS DON'T MATCH PRODUCT APPROVAL. | | B)DRAWINGS ARE NOT LEGIBLE. | | C)CHECK KEY PLAN AND INSTALLATION | | SCHEDULE WITH DRAWINGS SUBMITTED. | | 3-PROVIDE PRODUCT APPROVAL FOR: | | A)ENTRY DOORS PRODUCT APPROVAL AND DWGS | | ARE NOT LEGIBLE. (NOTE: CHECK THE | | EXPIRATION DATE FOR FUTURE SUBMITTALS. | | B)SINGLE HUNG FIRST PAGE OF PRODUCT | | APPROVAL DOESN'T MATCH THE REST OF THE | | REPORT AND DRAWINGS. RESUBMIT CORRECT | | COMPLETE REPORT AND DRAWINGS. | | 4-SPECIFY FIREBLOCKING LOCATION,MATERIAL | | AND SIZE AT STAIRS, INCLUDING FIRE- | | BLOCKING AT TOP OF STAIRS. SEE SEC. | | 2305.1.4 FBC 2001. | | 5-REVISE KEY NOTE #37 ON SHEET A-1. FULL | | HEIGHT WALL AS SHOWN ON EXTERIOR ELEV. | | TO COMPLY WITH TABLE 600 FBC 2001. | | 6-SECOND FLOOR FRAMING PLAN: SPECIFY | | DRAFSTOPPING AT AREAS NOT MORE THAN | | 500 S.F. AS REQUIRED BY SECTION | | 2305.2.2 FBC 2001. |
|