Plan Review Notes
Plan Review Notes For Permit 02060555
Permit Number 02060555
Review Stop R
Sequence Number 1
Notes
Date Text
2002-07-10 00:00:00CHECKLIST:
 1-NEED RECORDED NOTICE OF COMMENCEMENT.
 2-ENTRY DOORS DON'T PROVIDE THE 32" MIN.
 CLEAR OPENING REQUIRED BY TABLE 1004
 FBC 2001. REVISE AS REQUIRED.
 3-ENERGY CALCULATIONS:
 A)THERE IS NOT ADJACENT FRAME WALL. SEE
 PLANS AND REVISE AS REQUIRED.
 B)OWNER/AGENT TO DATE BOTTOM OF FORM TOO
 4-WINDOW BY ENTRY PORCH EXCEEDS THE MAX.
 PERCENTAGE OF OPENINGS ALLOWED BY
 TABLE 600 FBC 2001. REVISE AS REQUIRED
 5-SPECIFY FIREBLOCKING MATERIAL AND
 LOCATION AT STAIRS. SEC. 2305 FBC 2001
 **NOTE: FIREBLOCKING & DRAFSTOPPING ARE
 2 DIFFERENT THINGS.
 6-SPECIFY FIRECUT AT MASONRY WALL AS
 REQUIRED BY SEC. 2305.4 FBC 2001.
 7-2ND FL. FRAMING PLAN: SPECIFY MATERIAL
 & LOCATION OF DRAFSTOPPING AS REQUIRED
 BY SEC. 2305.2.2 FBC 2001.
 8-PROVIDE SOIL TEST REPORT.
 9-STORM SHUTTERS:
 A)PROVIDE COMPLETE INSTALLATION SCHEDULE
 AND KEY PLAN. SEE CITY COPY.
 B)CLEARLY INDICATE ON DRAWINGS SPECIFIC
 MOUNTING CONDITIONS AND ANCHOR TYPE &
 SPACING TO BE USED ACCORDING TO THE
 MEAN ROOF HEIGHT, DESIGN PRESSURES,
 EDGE DISTANCE, PANEL SPAN, CONNECTION
 TYPE AND STRUCTURE TO BE ATTACHED TO
 (CONCRETE BLOCK OR CONCRETE).
 10-PROVIDE PRODUCT APPROVAL FOR:
 A)ENTRY DOORS AS SHOWN ON PLANS.
 B)COMPLETE PANAMERICAN WINDOW MULLION
 PRODUCT APPROVAL.
 C)SINGLE HUNG WINDOW PRODUCT APPROVAL
 DOESN'T MATCH DRAWINGS.
  
 11-SHEET C-1 IS MISSING THE INTERNAL
 PRESSURE COEFFICIENT AS REQUIRED BY
 SEC. 1606.1.7 FBC 2001.
 12-APPROVED PRODUCT APPROVAL ARE STAMPED
 ALL OTHERS ARE RETURNED. SEE COMMENTS
 ON YELLOW STICKERS.