Plan Review Notes For Permit 02060553 |
Permit Number |
02060553 |
|
Review Stop |
M |
Sequence Number |
2 |
|
Notes |
Date |
Text |
2002-08-05 00:00:00 | PROVISO:MECHANICAL PERMIT 02060635 | | | | WHERE MULTIPLE AIR HANDLING SYSTEMS | | SHARE A COMMON SUPPLY OR RETURN AIR | | DUCTS OR PLENUMS WITH A COMBINED DESIGN | | CAPACITY GREATER THAN 2,000 CFM, THE | | RETURN & SUPPLY AIR SYSTEM SHALL BE | | PROVIDED WITH SMOKE DETECTORS IN | | ACCORDANCE WITH SECTION 606.2.1. | | | | SMOKE DETECTORS SHALL BE INSTALLED | | SUPPLY SYSTEMS WITH A DESIGN CAPACITY | | GREATER THAN 2,000 CFM, IN THE SUPPLY | | AIR DUCT. 2001 FBC(M) 606.2.1OR | | UPON ACTIVATION, THE SMOKE DETECTORS | | SHALL SHUTDOWN THE AIR DISTRIBUTION | | SYSTEM. 2001 FBC(M) 606.4 | | | | IF YOU HAVE ANY QUESTIONS, PLEASE | | CONTACT PATTY KRAUSS AT 659-8096 | | EXT. 8388. |
|