Plan Review Notes
Plan Review Notes For Permit 02060552
Permit Number 02060552
Review Stop R
Sequence Number 3
Notes
Date Text
2002-08-15 00:00:00BUILDING REVIEW APPROVED WITH PROVISO:
 1-PROVIDE ENGINEER'G ANALYSIS-CALCS FOR
 CLARIFICATION OF HOW THE MAIN WIND
 FORCE RESISTING SYSTEM (MWFRS) WAS
 DESIGNED TO RESIST AND TRANSFER ALL
 LOADS TO FLOOR AND CEILING DIAPHRAGMS
 CONSIDERING THE DOUBLE CEILING AREAS
 AND PARTIAL FLOOR DIAPHRAGM. SEE SEC.
 1606.2.4 FBC 2001.
 **PROVIDE ENGINEERING ANALYSIS/CALCS FOR
 CLARIFICATION OF MASONRY WALLS LATERAL
 STABILITY (SEC. 2105 FBC) AND LATERAL
 SUPPORT (SEC. 2107 FBC) CONSIDERING
 THE HIGH VOLUME AREA SHOWN ON PLANS.
 2-NEED FIREBLOCKING @ TOP OF STAIRS TOO.
 SEC. 2305.1.4 FBC. SPECIFY SIZE.
 3-PROVIDE SOIL TEST REPORT.
 4-NEED COMPLETE INFORMATION W/ LEGIBLE
 MATCHING PRODUCT APPROVAL AND DRAWINGS
 UNDER A SEPARATE PERMIT (INFORMATION
 WAS NOT COMPLETE AS REQUIRED BY CITY
 IMPLEMENTATION STANDARD FOR HURRICANE
 MISSILE IMPACT PROTECTION.
 5-PROVIDE LEGIBLE PRODUCT APPROVAL FOR
 DOORS, WINDOWS TO BE USED.
 **NOTE: SEE PLANS FOR RIGHT SIZE, SHAPE
 AND DESIGN PRESSURES.
 **ALSO, VERIFY THAT DRAWINGS IN PRODUCT
 APPROVALS MATCH THEIR REPORTS.
 6-PROVIDE 2X STRUCTURAL BUCK DETAIL FOR
 ARCHED WINDOWS AS REQUIRED BY THE
 PRODUCT APPROVAL.
 **NOTE: NEED DETAIL FOR FRAMED ARCH AND
 FOR MASONRY ATTACHMENT.
 7-NOTE 2 SHEET A-1: PROVIDE DETAIL THAT
 SHOWS WINDOW RECESSED 4.5" FOR THE
 INSTALLATION OF STORM SHUTTERS.
 **NOTE: SEE PRODUCT APPROVAL FOR TRACK
 USED CONSIDERING THE GLASS SEPARATION
 AND EDGE DISTANCE.
 8-SEE PRODUCT APPROVAL FOR GARAGE DOORS
 STRUCTURAL BUCK SPECS AND REVISE
 DETAIL AS REQUIRED.
 9-SPECIFY FIREBLOCKING IN WALL SECTIONS
 AND PROVIDE GENERAL SPECIFICATIONS FOR
 REQUIRED FIREBLOCKING AT ALL CONCEALED
 SPACES. SEC. 2305.1.4 FBC 2001.
 10-SPECIFY FIRECUT REQUIREMENTS ON THE
 STRUCTURAL WALL DETAILS AS WELL.
 SEC. 2305.4 FBC 2001.
 11-STAIR FLOOR PLAN: CLARIFY NOTE #13.
 REVISE STAIR DETAILS. REMEMBER THAT
 WOOD COLUMN WILL BE CHANGED FOR STEEL
 COLUMN. ALSO, VERIFY THAT KEY NOTES
 FOR STAIRS MATCH THE DETAILS.
 12-SPECIFY SPACING FOR WWM SUPPORTS. SEE
 SECTION 1909.3 FBC 2001.
 13-SHEET S-1: SOME DETAILS AND NOTES ARE
 OVERLAPPING OR DETAILS NOT SHOWN.
 14-SHEET S-3: IDENTIFY ROOF ZONE 3 FOR
 NAILING DIAPHRAGM.
 **REVISE TRUSS CONNECTOR SCHEDULE:
 NUMBER OF FASTENERS SPECIFIED AND
 ALLOWABLE UPLIFT DON'T MATCH. SEE USP
 CATALOGUE. PROVIDE ENGINEERED CALCS
 FOR UPLIFT LOADS DIFFERENT THAN THOSE
 SPECIFIED ON CATALOGUE.
 15-PROVIDE ATTIC ACCESS ABOVE GARAGE AND
 MORNING ROOM IF CLEAR HEIGHT IS MORE
 THAN 24". SEC. 2309.6 FBC 2001.