2002-08-15 00:00:00 | BUILDING REVIEW APPROVED WITH PROVISO: |
| 1-PROVIDE ENGINEER'G ANALYSIS-CALCS FOR |
| CLARIFICATION OF HOW THE MAIN WIND |
| FORCE RESISTING SYSTEM (MWFRS) WAS |
| DESIGNED TO RESIST AND TRANSFER ALL |
| LOADS TO FLOOR AND CEILING DIAPHRAGMS |
| CONSIDERING THE DOUBLE CEILING AREAS |
| AND PARTIAL FLOOR DIAPHRAGM. SEE SEC. |
| 1606.2.4 FBC 2001. |
| **PROVIDE ENGINEERING ANALYSIS/CALCS FOR |
| CLARIFICATION OF MASONRY WALLS LATERAL |
| STABILITY (SEC. 2105 FBC) AND LATERAL |
| SUPPORT (SEC. 2107 FBC) CONSIDERING |
| THE HIGH VOLUME AREA SHOWN ON PLANS. |
| 2-NEED FIREBLOCKING @ TOP OF STAIRS TOO. |
| SEC. 2305.1.4 FBC. SPECIFY SIZE. |
| 3-PROVIDE SOIL TEST REPORT. |
| 4-NEED COMPLETE INFORMATION W/ LEGIBLE |
| MATCHING PRODUCT APPROVAL AND DRAWINGS |
| UNDER A SEPARATE PERMIT (INFORMATION |
| WAS NOT COMPLETE AS REQUIRED BY CITY |
| IMPLEMENTATION STANDARD FOR HURRICANE |
| MISSILE IMPACT PROTECTION. |
| 5-PROVIDE LEGIBLE PRODUCT APPROVAL FOR |
| DOORS, WINDOWS TO BE USED. |
| **NOTE: SEE PLANS FOR RIGHT SIZE, SHAPE |
| AND DESIGN PRESSURES. |
| **ALSO, VERIFY THAT DRAWINGS IN PRODUCT |
| APPROVALS MATCH THEIR REPORTS. |
| 6-PROVIDE 2X STRUCTURAL BUCK DETAIL FOR |
| ARCHED WINDOWS AS REQUIRED BY THE |
| PRODUCT APPROVAL. |
| **NOTE: NEED DETAIL FOR FRAMED ARCH AND |
| FOR MASONRY ATTACHMENT. |
| 7-NOTE 2 SHEET A-1: PROVIDE DETAIL THAT |
| SHOWS WINDOW RECESSED 4.5" FOR THE |
| INSTALLATION OF STORM SHUTTERS. |
| **NOTE: SEE PRODUCT APPROVAL FOR TRACK |
| USED CONSIDERING THE GLASS SEPARATION |
| AND EDGE DISTANCE. |
| 8-SEE PRODUCT APPROVAL FOR GARAGE DOORS |
| STRUCTURAL BUCK SPECS AND REVISE |
| DETAIL AS REQUIRED. |
| 9-SPECIFY FIREBLOCKING IN WALL SECTIONS |
| AND PROVIDE GENERAL SPECIFICATIONS FOR |
| REQUIRED FIREBLOCKING AT ALL CONCEALED |
| SPACES. SEC. 2305.1.4 FBC 2001. |
| 10-SPECIFY FIRECUT REQUIREMENTS ON THE |
| STRUCTURAL WALL DETAILS AS WELL. |
| SEC. 2305.4 FBC 2001. |
| 11-STAIR FLOOR PLAN: CLARIFY NOTE #13. |
| REVISE STAIR DETAILS. REMEMBER THAT |
| WOOD COLUMN WILL BE CHANGED FOR STEEL |
| COLUMN. ALSO, VERIFY THAT KEY NOTES |
| FOR STAIRS MATCH THE DETAILS. |
| 12-SPECIFY SPACING FOR WWM SUPPORTS. SEE |
| SECTION 1909.3 FBC 2001. |
| 13-SHEET S-1: SOME DETAILS AND NOTES ARE |
| OVERLAPPING OR DETAILS NOT SHOWN. |
| 14-SHEET S-3: IDENTIFY ROOF ZONE 3 FOR |
| NAILING DIAPHRAGM. |
| **REVISE TRUSS CONNECTOR SCHEDULE: |
| NUMBER OF FASTENERS SPECIFIED AND |
| ALLOWABLE UPLIFT DON'T MATCH. SEE USP |
| CATALOGUE. PROVIDE ENGINEERED CALCS |
| FOR UPLIFT LOADS DIFFERENT THAN THOSE |
| SPECIFIED ON CATALOGUE. |
| 15-PROVIDE ATTIC ACCESS ABOVE GARAGE AND |
| MORNING ROOM IF CLEAR HEIGHT IS MORE |
| THAN 24". SEC. 2309.6 FBC 2001. |