Plan Review Notes
Plan Review Notes For Permit 02060552
Permit Number 02060552
Review Stop R
Sequence Number 2
Notes
Date Text
2002-08-08 00:00:00CHECKLIST:
 1-PROVIDE ENGINEERING CALCULATIONS AND
 DIAGRAMS SHOWING HOW ARE EXTERIOR
 WALLS DESIGNED FOR LATERAL STABILITY
 (SHEAR WALLS) SEC. 2105 FBC AND FOR
 LATERAL SUPPORT AS REQUIRED ON SECTION
 2107 FBC. CLARIFY HOW ARE WIND LOADS
 TRANSFERED TO THE ROOF AND FLOOR
 DIAPHRAGMS. (SEC. 104.2.1.2 CITY
 AMENDMENTS TO FBC 2001.
 2-CLARIFY CONNECTION AT POST P1. PROVIDE
 CALCULATIONS SHOWING THAT CONNECTORS
 (TOP AND BOTTOM) WILL RESIST THE LOADS
 TRANSFERED FROM THE FLOOR DIAPHRAGM.
 SEC. 104.2.1.2 CITY AMENDMENTS TO FBC
 3-CLARIFY COL. SCHEDULE. P1 IS 6X8 POST.
 WHAT IS 4X10 W/ 2X10 NAILED TOGETHER?
 ALSO, USP PA66 IS NOT GOOD FOR A 6X8
 POST. REVISE AS REQUIRED.
 4-NEED RECORDED NOTICE OF COMMENCEMENT.
 5-SPECIFY FIREBLOCKING AT TOP OF STAIRS.
 SEC. 2305.2.2 FBC 2001.
 NOTE: DRAW TOP & BOTTOM TRUSS CHORD TO
 SCALE TO CLARIFY DETAIL.
 6-NEED SIGNED & SEALED SOIL TEST REPORT.
 7-STORM SHUTTERS:
 A)DRAWINGS DON'T MATCH REPORT AND ARE
 NOT LEGIBLE.
 B)CHECK KEY PLAN AND INSTALLATION SCHED.
 WITH ACTUAL PLANS SUBMITTED.
 8-PROVIDE PRODUCT APPROVAL FOR:
 A)ENTRY DOORS W/ LEGIBLE REPORT & DWGS.
 B)SINGLE HUNG WINDOWS FIRST PAGE OF
 REPORT DOESN'T MATCH THE REST.
 C)ARCHED WINDOWS. SEE SIZES SHOWN ON
 PLANS.
 9-PROVIDE 2X STRUCTURAL BUCK DETAIL FOR
 ARCHED WINDOWS AS REQUIRED BY PRODUCT
 APPROVAL. NOTE DETAIL SUBMITTED IS NOT
 CORRECT. SEE ARCHED OPENINGS. THERE IS
 NOT FRAMED WALL. REVISE AS REQUIRED.
 10-SHEET C1 WAS NOT CHANGED.
 11-PROVIDE COMPLETE DETAILS & SPECS FOR
 FRAMED WALLS SHOWING HOW ARE SHEAR
 WALLS TRANSFERING THE LOADS. SEE SEC.
 2313 FBC 2001.