2002-06-18 00:00:00DENIED:MECHANICAL PERMIT 02060565
  
 PLEASE CLARIFY ENERGY CALCS, CENTRAL
 UNIT B. CAPCITY 16.7 BTU/HR.PLAN
 INDICATES A 3 TON UNIT.MANUAL J CALCS
 DO NOT INDICATE 2 SYSTEMS.
  
 SHOW COMPLIANCE FOR COMBUSTION AIR AS
 PER 2001 FBC(M) CHAPTER 7.
  
 CONDENSATE SHALL DISCHARGE A MINIMUM OF
 12" AWAY FROM THE BUILDING STRUCTURE AS
 PER 2001 FBC 1503.4.4.
  
 APPLIANCES SHALL NOT BE INSTALLED IN A
 LOCATION WHERE SUBJECT TO MECHANICAL
 DAMAGE UNLESS PROTECTED BY APPROVED
 BARRIERS.2001 FBC(M) 303.4
  