Plan Review Notes For Permit 02060533 |
Permit Number |
02060533 |
|
Review Stop |
M |
Sequence Number |
1 |
|
Notes |
Date |
Text |
2002-06-18 00:00:00 | DENIED:MECHANICAL PERMIT 02060565 | | | | PLEASE CLARIFY ENERGY CALCS, CENTRAL | | UNIT B. CAPCITY 16.7 BTU/HR.PLAN | | INDICATES A 3 TON UNIT.MANUAL J CALCS | | DO NOT INDICATE 2 SYSTEMS. | | | | SHOW COMPLIANCE FOR COMBUSTION AIR AS | | PER 2001 FBC(M) CHAPTER 7. | | | | CONDENSATE SHALL DISCHARGE A MINIMUM OF | | 12" AWAY FROM THE BUILDING STRUCTURE AS | | PER 2001 FBC 1503.4.4. | | | | APPLIANCES SHALL NOT BE INSTALLED IN A | | LOCATION WHERE SUBJECT TO MECHANICAL | | DAMAGE UNLESS PROTECTED BY APPROVED | | BARRIERS.2001 FBC(M) 303.4 | | | | IF YOU HAVE ANY QUESTIONS, PLEASE | | CONTACT PATTY KRAUSS AT 659-8096 | | EXT. 8388. |
|