| BUILDING PLAN REVIEW |
| PERMIT: 02060509 |
| ADD: 7592 IRONHORSE BLVD |
| CONT: ANTHONY & SYLVAN |
| TEL: 686-7946 |
| FL BLD CODE= 2001 FLORIDA BUILDING CODE |
| |
| 1)1803.1.3 EXCAVATION FOR ANY PURPOSE |
| SHALL NOT EXTEND WITHIN 1 FT OF THE |
| ANGLE OF REPOSE OR NARURAL SLOPE OF THE |
| SOIL UNDER ANY FOOTING OR FOUNDATION, |
| UNLESS SUCH FOOTING OR FOUNDATION IS |
| FIRST PROPERLY UNDERPINNED OR PROTECTED |
| AGAINST SETTLEMENT. INDICATE WHAT TYPE |
| OF PROTECTION SHALL BE USED AGAINST |
| SETTLMENT? |
| |
| 2) CHAP.13-612.ABC2.3.2 COVERS REQUIRED |
| SPAS AND HEATED SWIMMING POOLS SHALL BE |
| EQUIPPED WITH A COVER DESIGNED TO MINI- |
| MIZE HEAT LOSS. |
| |
| 4) FBC-2001 SEC 424.2.6.6 ENTRAPMENT |
| PROTECTION FOR SUCTION INLETS. (DETAIL) |
| |
| 5) FBC 424.2.17.1.9 WHERE A WALL OR |
| DWELLING SERVES AS PART OF THE BARRIER, |
| PROVIDE INFORMATION AS TO HOW PROTECTION |
| OF OPENINGS SHALL BE MAINTAINED? |
| |
| LOOK FOR COMMENTS BY THE OTHER PLAN |
| REVIEW DISCIPLINES THAT MAY BE WRITTEN |
| ON THE APPLICATION, PLANS, OR ATTACHED |
| SEPARATELY. WHEN RESUBMITTING PLANS |
| PLEASE CLEARLY INDICATE THE REVISION AND |
| REMOVE AND REPLACE ANY PAGES AS NECESS- |
| ARY. A TRANSMITTAL LETTER LISTING THE |
| ORIGINAL REVIEW COMMENT NUMBER, WITH A |
| DESCRIPTION OF THE REVISION MADE, IDEN- |
| TIFYING THE SHEET OR SPECIFICATION PAGE |
| WHERE THE CHANGES CAN BE FOUND, WILL |
| HELP TO EXPEDITE YOUR PERMIT. THANK YOU |
| FOR YOUR ANTICIPATED COOPERATION. |
| JIM WITMER |
| PLAN REVIEW |
| TEL: (561)659-8096 EX.8412 |