Plan Review Notes
Plan Review Notes For Permit 02060490
Permit Number 02060490
Review Stop B
Sequence Number 2
Notes
Date Text
2002-10-15 00:00:00SHEET A-1.0"CONSTRUCTION TYPE"THE
 CONSTRUCTION TYPE OF THIS BUILDING IS
 TYPEI, FIRE SPRINKLERED NOT THE TYPE IV
 UNPROTECTED DECLARED.THE HEIGHT
 EXCEEDS 80'.
  
  
 PROVIDE AN ELEVATOR LOBBY IN ACCORDANCE
 WITH FBC 412.6.
  
 SHOW EXISTING ATRIUM FACILITIES AS
 COMPLYING WITH FBC 414 OR A SHAFT
 ENCLOSURE INACCORDANCE WITH FBC 705.2.2
 FOR THE AREA SHOWN AS "OPEN TO BELOW"