2002-06-12 00:00:00 | *******************DENIED*************** |
| |
| PLEASE PROVIDE THE FOLLOWING INFORMATION |
| FOR REVIEW. |
| |
| 1.INDICATE LOCATIONS OF ANY NEW FIRE |
| DAMPERS TO BE INSTALLED AS PER 2001 |
| FBC(M) 607.6.THE FOLLOWING ARE A |
| LIST OF PENETRATIONS IN QUESTION. |
| CORRIDOR 549 - PLANS SHEET A-2.1 |
| INDICATES 1HR. CONFERENCE RM 562 HR |
| RATING.PLANS ARE UNCLEAR AS TO THE |
| RATING OF MECHANICAL, ELECTRICAL & |
| STORAGE ROOM.PLEASE CLARIFY. |
| |
| 2.PLEASE PROVIDE OUTSIDE AIR CALCS AS |
| PER 2001 FBC(M) TABLE 403.3 OR |
| ASHRAE 62-89. |
| |
| 3.AS PER 2001 FBC(M) 602.2.1 MATERIALS |
| EXPOSED WITHIN PLENUMS SHALL BE NON- |
| COMBUSTIBLE OR SHALL HAVE A FLAME |
| SPREAD INDEX OF NOT MORE THAN 25 & |
| A SMOKE-DEVELOPED INDEX OF NOT MORE |
| THAN 50 WHEN TESTED IN ACCORDANCE |
| WITH ASTM E 84. |
| |
| 4.PRESSURE DIFFIERENTIALS ACROSS |
| CLOSED DOORS SHALL BE LIMITED TO |
| .001 IN WC OR LESS.PROVIDE AIR |
| TRANSFER PATHWAYS OR AIR DUCT PATH- |
| WAYS FOR COMPLIANCE. 2001 FBC(M) |
| 601.4 |
| |
| 5.INDICATE DUCT SMOKE DETECTORS ON |
| PLAN - NEW OR EXISTING. |
| |
| IF YOU HAVE ANY QUESTIONS, PLEASE |
| CONTACT PATTY KRAUSS AT 659-8096 |
| EXT. 8388. |