Plan Review Notes
Plan Review Notes For Permit 02060490
Permit Number 02060490
Review Stop M
Sequence Number 1
Notes
Date Text
2002-06-12 00:00:00*******************DENIED***************
  
 PLEASE PROVIDE THE FOLLOWING INFORMATION
 FOR REVIEW.
  
 1.INDICATE LOCATIONS OF ANY NEW FIRE
 DAMPERS TO BE INSTALLED AS PER 2001
 FBC(M) 607.6.THE FOLLOWING ARE A
 LIST OF PENETRATIONS IN QUESTION.
 CORRIDOR 549 - PLANS SHEET A-2.1
 INDICATES 1HR. CONFERENCE RM 562 HR
 RATING.PLANS ARE UNCLEAR AS TO THE
 RATING OF MECHANICAL, ELECTRICAL &
 STORAGE ROOM.PLEASE CLARIFY.
  
 2.PLEASE PROVIDE OUTSIDE AIR CALCS AS
 PER 2001 FBC(M) TABLE 403.3 OR
 ASHRAE 62-89.
  
 3.AS PER 2001 FBC(M) 602.2.1 MATERIALS
 EXPOSED WITHIN PLENUMS SHALL BE NON-
 COMBUSTIBLE OR SHALL HAVE A FLAME
 SPREAD INDEX OF NOT MORE THAN 25 &
 A SMOKE-DEVELOPED INDEX OF NOT MORE
 THAN 50 WHEN TESTED IN ACCORDANCE
 WITH ASTM E 84.
  
 4.PRESSURE DIFFIERENTIALS ACROSS
 CLOSED DOORS SHALL BE LIMITED TO
 .001 IN WC OR LESS.PROVIDE AIR
 TRANSFER PATHWAYS OR AIR DUCT PATH-
 WAYS FOR COMPLIANCE. 2001 FBC(M)
 601.4
  
 5.INDICATE DUCT SMOKE DETECTORS ON
 PLAN - NEW OR EXISTING.
  
 IF YOU HAVE ANY QUESTIONS, PLEASE
 CONTACT PATTY KRAUSS AT 659-8096
 EXT. 8388.