Plan Review Notes For Permit 02060490 |
Permit Number |
02060490 |
|
Review Stop |
FIRE |
Sequence Number |
1 |
|
Notes |
Date |
Text |
2002-06-28 00:00:00 | 1) PLEASE INDICATE WHAT "TEMPORARY" | | MEANS WITH REGARDS TO DURATION. | | | | 2) PLASTIC MATERIAL PLANNED TO BE HUNG | | FROM FLOOR SLAB IF NOT FIRE RETARDANT | | WILL NOT BE PERMITTED. | | | | 3) DEBRIS FROM DEMOLITION SHALL BE | | REMOVED FROM THE BUILDING DAILY. | | | | 4) ALL EXITS AND EXIT ACCESS CORRIDORS | | ARE TO BE MAINTAINED AT ALL TIMES | | DURING CONSTRUCTION. | | | | 5) ALL FIRE SAFETY EQUIPMENT ARE TO | | REMAIN IN OPERATION DURING DEMOLITION, | | RENOVATION, AND DEMOLITION. | | | | 6) DEAD-END CORRIDORS AND TRAVEL | | DISTANCES TO EXITS ARE NOT TO BE | | EXCEEDED FOR ANY REASONS. | | | | 7) PLEASE PROVIDE FLAMESPREAD DATA ON | | TEMPORARY ISOLATION WALLS. | | | | 8) NO GASOLINE POWERED EQUIPMENT IS TO | | BE USED DUE TO INADEQUATE VENTILATION. | | CARBON MONOXIDE EXPOSURE BECOMES A | | SAFETY ISSUE. | | | | 9) PLEASE INDICATE INTERIOR FINISH | | CLASSIFICATION INFORMATION FOR WALLS | | AND CEILINGS. | | | | 10) PLANS SHALL DELINEATE THE REQUIRED | | FORTY FOUR INCH WIDTH ESPECIALLY | | BETWEEN WORK STATIONS. | | | | MIKE CARSILLO, ASSISTANT FIRE MARSHAL | | 659-8096,EXT.8497 | | 835-2910 |
|