2002-06-28 00:00:00 | DENIED |
| REFERENCE: FBC-2001 CHAPTER 11 |
| FBC-2001 PLUMBING |
| |
| 1) A DRINKING FOUNTAIN AND A SERVICE |
| SINK ARE REQUIRED PER TABLE 403.1 |
| SEE 11-4.15 AND 11-4.1.3(10) PROVIDE |
| DETAILS FOR DRINKING FOUNTAIN. |
| 2) SHT A3 DETAIL #4, SINK TO COMPLY WITH |
| 11-4.24 PROVIDE DETAILS. |
| 3) SHT A3 DETAIL #3, URNAL SHALL COMPLY |
| WITH 11-4.18.2, MAX HEIGHT 17". SHOW ON |
| DETAIL. |
| 4) SHT P-1 KEYNOTE (2) 2-1/2" AND SMALL- |
| ER PIPE SHALL BE RUN AT 1/4" PER FOOT |
| PER TABLE 704.1. PLEASE CHANGE NOTE. |
| 5) SHTS P-1/P-2 WATER HEATER DETAIL, PER |
| 504.7.1 THE RELIEF (T/P) DISCHARGE LINE |
| SHALL NOT HAVE ANY TRAPPED SECTIONS AND |
| SHALL HAVE A VISIBLE AIR GAP OR AIR GAP |
| FITTING LOCATED IN THE SAME ROOM AS THE |
| WATER HEATER. PROVIDE DETAILS. |
| 6) SHT P-1 WATER ISOMETRIC SHOWS TWO 1/2 |
| INCH COLD LINES RUN TO A SINK NOT SHOWN |
| ON THE FLOOR PLAN. PLEASE CLAIRFY. |
| 7) SHT P-1 WATER ISOMETRIC, AIR CHAMBERS |
| ARE NOT APPROVED. WATER HAMMERS ARE RE- |
| QUIRED FOR ALL QUICK CLOSING VALVES PER |
| 604.9. (SEE SHT P-2 PLUMBING SYMBOLS & |
| ABBREVIATIONS) |
| 8) SHT P-1 SANITARY ISOMETRIC DOES NOT |
| REFLECT THE FLOOR PLAN. FLOOR DRAINS |
| PRIOR TO BACK TO BACK URNAL AND WATER |
| CLOSET ARE NOT SHOWN ON SANT. ISO. |
| |