2002-06-28 00:00:00DENIED
 REFERENCE: FBC-2001 CHAPTER 11
 FBC-2001 PLUMBING
  
 1) A DRINKING FOUNTAIN AND A SERVICE
 SINK ARE REQUIRED PER TABLE 403.1
 SEE 11-4.15 AND 11-4.1.3(10) PROVIDE
 DETAILS FOR DRINKING FOUNTAIN.
 2) SHT A3 DETAIL #4, SINK TO COMPLY WITH
 11-4.24 PROVIDE DETAILS.
 3) SHT A3 DETAIL #3, URNAL SHALL COMPLY
 WITH 11-4.18.2, MAX HEIGHT 17". SHOW ON
 DETAIL.
 4) SHT P-1 KEYNOTE (2) 2-1/2" AND SMALL-
 ER PIPE SHALL BE RUN AT 1/4" PER FOOT
 PER TABLE 704.1. PLEASE CHANGE NOTE.
 5) SHTS P-1/P-2 WATER HEATER DETAIL, PER
 504.7.1 THE RELIEF (T/P) DISCHARGE LINE
 SHALL NOT HAVE ANY TRAPPED SECTIONS AND
 SHALL HAVE A VISIBLE AIR GAP OR AIR GAP
 FITTING LOCATED IN THE SAME ROOM AS THE
 WATER HEATER. PROVIDE DETAILS.
 6) SHT P-1 WATER ISOMETRIC SHOWS TWO 1/2
 INCH COLD LINES RUN TO A SINK NOT SHOWN
 ON THE FLOOR PLAN. PLEASE CLAIRFY.
 7) SHT P-1 WATER ISOMETRIC, AIR CHAMBERS
 ARE NOT APPROVED. WATER HAMMERS ARE RE-
 QUIRED FOR ALL QUICK CLOSING VALVES PER
 604.9. (SEE SHT P-2 PLUMBING SYMBOLS &
 ABBREVIATIONS)
 8) SHT P-1 SANITARY ISOMETRIC DOES NOT
 REFLECT THE FLOOR PLAN. FLOOR DRAINS
 PRIOR TO BACK TO BACK URNAL AND WATER
 CLOSET ARE NOT SHOWN ON SANT. ISO.
  
 REVIEW BY KEN STEVENS