2002-06-19 00:00:00**************** UNSAT *****************
  
 1)NOTE: PLEASE NOTE SHOWN EXCEEDS RATING
 OF SERVICE ENTRANCE CONDUCTORS. PLEASE
 NOTE SIZINGPER 310-16.
 SHOWS 2-SETS OF 500MCM, RATED AT 380A`S
 EACH= 760AMPS. PLEASE NOTE 769A SHOWN
 ON LOAD CALCS AND HAS ONLY AN EST FOR
 FUTURE TENANT "OUTREACH".
 PLEASE SHOW A COMPLETE LOAD CALCULATION
 FOR BLDG. PER 220
  
 2)NOTE: PLEASE PLACE NOTE ON PLANS FOR
 LABELING OF DISCONNECTING MEANS OF
 GENERATOR. INSIDE ELECTRICAL ROOM AND
 OUTSIDE BY MAIN SERVICE. 230-2 E
  
 PLEASE JUST NOTE A MISPRINT FOR PANEL "G
 , PLEASE NOTE SHOWN AS "GP" ON RISER
 DIAGRAM.
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE CALL.
  