1 |
|
Notes |
Date |
Text |
2002-06-19 00:00:00 | **************** UNSAT ***************** | | | | 1)NOTE: PLEASE NOTE SHOWN EXCEEDS RATING | | OF SERVICE ENTRANCE CONDUCTORS. PLEASE | | NOTE SIZINGPER 310-16. | | SHOWS 2-SETS OF 500MCM, RATED AT 380A`S | | EACH= 760AMPS. PLEASE NOTE 769A SHOWN | | ON LOAD CALCS AND HAS ONLY AN EST FOR | | FUTURE TENANT "OUTREACH". | | PLEASE SHOW A COMPLETE LOAD CALCULATION | | FOR BLDG. PER 220 | | | | 2)NOTE: PLEASE PLACE NOTE ON PLANS FOR | | LABELING OF DISCONNECTING MEANS OF | | GENERATOR. INSIDE ELECTRICAL ROOM AND | | OUTSIDE BY MAIN SERVICE. 230-2 E | | | | PLEASE JUST NOTE A MISPRINT FOR PANEL "G | | , PLEASE NOTE SHOWN AS "GP" ON RISER | | DIAGRAM. | | | | PLEASE SUBMIT THE ABOVE INFORMATION FOR | | REVIEW. IF THERE ARE ANY QUESTIONS, | | PLEASE CALL. | | | | DEWEY PALMER | | ELECTRICAL PLAN REVIEW | | 561-659-8096 EXT 8372 |
|