Plan Review Notes For Permit 02060381 |
Permit Number |
02060381 |
|
Review Stop |
B |
Sequence Number |
96 |
|
Notes |
Date |
Text |
2005-01-21 00:00:00 | ****CORRECTIONS**** | | REVISED AWNING SHOPS | | PREPARED BY L.TYLKA, PE | | | | SAMANTHA HILL, BUILDING PLANS EXAMINER | | [email protected] | | | | 1.)THE ICBO SUBMITTED (REPORT NO. | | 1372, JUNE 1992) IS EXPIRED.THE | | CURRENT REPORT IS MARCH 2000.CANNOT | | USE EXPIRED REPORTS AS JUSTIFICATION. | | | | 2.)PLEASE DIFFERENTIATE BETWEEN | | GRAVITY LOAD AND WIND LOAD IN THE | | LETTER | | (PARAGRAPH 2).WHICH IS THE WORST | | LOADING CASE, GRAVITY OR WIND?BASED | | ON | | OUR TELEPHONE CONVERSATION, THE ANCHORS | | WERE DOUBLED AS A RESULT OF LOSS OF | | CAPACITY DUE TO SUBSTRATE CONDITIONS. | | THE PLAN SHOWS ADDITIONAL ANCHORS AT | | THE | | BOTTOM ONLY. DOES THIS MEAN THAT THE | | SAME ANCHORS AT THE TOP SPECIFIED FOR | | CONCRETE WERE SUFFICIENT FOR HOLLOW | | BLOCK FOR GRAVITY LOADS? | | | | I THANK YOU FOR YOUR PATIENCE AND | | CONTINUING ASSISTANCE IN RESOLVING THIS | | MATTER.PLEASE FEEL FREE TO CONTACT ME | | AT YOUR CONVENIENCE SHOULD YOU NEED | | ADDITIONAL INFORMATION. |
|