2005-01-21 00:00:00****CORRECTIONS****
 REVISED AWNING SHOPS
 PREPARED BY L.TYLKA, PE
  
 SAMANTHA HILL, BUILDING PLANS EXAMINER
 [email protected]
  
 1.)THE ICBO SUBMITTED (REPORT NO.
 1372, JUNE 1992) IS EXPIRED.THE
 CURRENT REPORT IS MARCH 2000.CANNOT
 USE EXPIRED REPORTS AS JUSTIFICATION.
  
 2.)PLEASE DIFFERENTIATE BETWEEN
 GRAVITY LOAD AND WIND LOAD IN THE
 LETTER
 (PARAGRAPH 2).WHICH IS THE WORST
 LOADING CASE, GRAVITY OR WIND?BASED
 ON
 OUR TELEPHONE CONVERSATION, THE ANCHORS
 WERE DOUBLED AS A RESULT OF LOSS OF
 CAPACITY DUE TO SUBSTRATE CONDITIONS.
 THE PLAN SHOWS ADDITIONAL ANCHORS AT
 THE
 BOTTOM ONLY. DOES THIS MEAN THAT THE
 SAME ANCHORS AT THE TOP SPECIFIED FOR
 CONCRETE WERE SUFFICIENT FOR HOLLOW
 BLOCK FOR GRAVITY LOADS?
  
 I THANK YOU FOR YOUR PATIENCE AND
 CONTINUING ASSISTANCE IN RESOLVING THIS
 MATTER.PLEASE FEEL FREE TO CONTACT ME
 AT YOUR CONVENIENCE SHOULD YOU NEED
 ADDITIONAL INFORMATION.