2005-01-06 00:00:00****CORRECTIONS****
  
 SAMANTHA HILL, BUILDING PLANS EXAMINER
 [email protected]
 CALCS FOR HOUSEKEEPING PAD AND 6TH
 STORY
 STEEL DECK
  
 1.)THE ACI REFERENCE USED MUST BE IN
 ACCORDANCE WITH FBC CHAPTER 35, WHICH
 REFERENCES ACI 318-02.THE INFORMATION
 SUBMITTED WAS FROM ACI 318-93.
  
 2.)THE CALCS STILL SHOW 4.22%
 OVERSTRESS (WAS 2% PREVIOUSLY), WITH
 THE
 WATER AS A DEAD LOAD.THE CALCS
 SUBMITTED MUST BE COMPLIANT WITH
 FBC1601.2.1.IF THE CONCRETE WAS
 STRONGER THAN DESIGN SPECIFIED, AND
 THIS
 IS YOUR JUSTIFICATION, PLEASE INCLUDE
 IT
 IN THE CALCS TO SHOW CODE COMPLIANCE.
  
 3.)WHY WILL THE HOT WATER TANK NOT BE
 FULL 99% OF THE TIME?DOES THIS TANK
 WORK DIFFERENTLY FROM OTHER TANKS,
 WHICH
 REFILL AS HOT WATER LEAVES THE TANK, SO
 ARE ALWAYS FULL?IF THE WATER LEVEL
 CHANGES WITHIN THE TANK, HOW DOES THE
 TANK ADDRESS THE VACUUM CREATED?
 PLEASE
 SUBMIT PRODUCT DATA FOR CLARIFICATION.
 THE CALCS WERE RUN AT 90% FULL; PROVIDE
 SOME DOCUMENTATION FOR THIS ASSUMPTION.
  
 4.)PLEASE NOTE THAT THE ORIGINAL CALCS
 SUBMITTED (WITH A MATH ERROR, AND TANK
 AS A DEAD LOAD) WHEN RUN WITHOUT THE
 MATH ERROR AND THE TANK AS A LIVE LOAD
 APPEARS TO SHOW A 28% OVERSTRESS.
  
 5.)IN ADDRESSING THE COMMENT
 REGARDING
 THE STEEL DECK, I BELIEVE YOU ARE
 STATING THAT THE DENSGLASS CAN ACT WITH
 THE STEEL DECK AS THE MWFRS.THE CALCS
 CANNOT SHOW AN OVERSTRESS, FBC1601.2.1.
 ALSO YOUR NOTE STATES THAT THE
 DENSGLASS
 AT 3.5PSF WILL ACCOUNT FOR THE 2%
 INADEQUACY, BUT ISN'T THE STEEL DECK
 3.5% OVERSTRESSED?PLEASE RERUN THE
 CALCULATIONS INCLUDING THE DENSGLASS IF
 THAT IS HOW YOU ARE SHOWING CODE
 COMPLIANCE.
  
  
  
 SENT VIA FAX TO PAUL KING, PE AND TO
 WHITING TURNER