Plan Review Notes For Permit 02060381 |
Permit Number |
02060381 |
|
Review Stop |
B |
Sequence Number |
85 |
|
Notes |
Date |
Text |
2004-12-09 00:00:00 | ****CORRECTIONS**** | | HOUSEKEEPING PAD, STEEL DECK | | CALCULATIONS; DOOR PRODUCT APPROVALS & | | SHOPS | | | | | | SAMANTHA HILL, BUILDING PLANS EXAMINER | | [email protected] | | | | 1.)FBC1601.2.1 EVERY BUILDING AND | | STRUCTURE SHALL BE OF SUFFICIENT | | STRENGTH TO | | SUPPORT THE LOADS AND FORCES | | ENCOUNTERED, OR COMBINATIONS THEREOF, | | WITHOUT | | EXCEEDING IN ANY OF ITS STRUCTURAL | | ELEMENTS THE STRESSES PRESCRIBED | | ELSEWHERE IN THIS CODE.CALCULATIONS | | SUBMITTED WHICH INDICATE 2% | | (HOUSEKEEPING PAD) AND 5% (STEEL ROOF | | DECK) OVERSTRESSES ARE NOT CODE | | COMPLIANT.PLEASE ADDRESS. | | | | 2.)SEE PREVIOUS CORRECTION LISTS. | | PRODUCT APPROVALS SUBMITTED ARE | | COMPLIANT FOR ZONE 4 BUT NOT FOR ZONE 5. | | I CANNOT DETERMINE FROM THE PLAN WHERE | | ZONE 5 IS.PLEASE PROVIDE INFORMATION | | REQUESTED - OF THE OPENINGS, WHICH ONES, | | IF ANY, ARE IN ZONE 5? | | |
|