2004-07-28 00:00:00 | ****CORRECTIONS**** |
| SLIDING GLASS DOOR SUBMITTAL & SHOPS |
| DENIED PRODUCT APPROVALS (DOORS, AUTO) |
| |
| SAMANTHA HILL, BUILDING PLANS EXAMINER |
| [email protected] |
| |
| 1.)SHEETS REGARDING THE SLIDING |
| GLASS DOOR HAVE BEEN REMOVED FROM THE |
| APPROVED SUBMITTAL; SHEETS 19, 20, R1, |
| R2, R3, R4 (FROM CALCS), SHEETS 9-11, |
| 17-19 (FROM SHOPS).PROVIDE TEST |
| REPORT FBC1707.4.2. |
| |
| 2.)SEE THE CORRECTION LIST DATED 4/12 |
| IN REGARDS TO SOME OF THE DOOR PRODUCT |
| APPROVAL PRESSURE LIMITATIONS.THIS |
| COMMENT WAS ADDRESSED BY AL-FAROOQ FOR |
| THE WINDOWS, BUT HAS NOT BEEN ADDRESSED |
| FOR THE FOLLOWING ITEMS: |
| |
| STEELCRAFT L18 4 3070 FG DOOR - |
| TEST REPORT FROM CERTIFIED TESTING |
| LABORATORIES PROVIDES DESIGN PRESSURES |
| OF +-50 AND +-60. |
| |
| STEELCRAFT SERIES L,SL,CE & B NOA |
| NUMBER 01-0129.10.THIS DOOR IS |
| COMPLIANT ONLY WHERE WATER INFILTRATION |
| IS NOT REQUIRED, ZONE 4. |
| |
| SERIES 800 SERVICE DOOR, NOA |
| 01-1031.08, +-56; COMPLIANT ONLY FOR |
| ZONE 4. |
| |
| HORTON AUTOMATICS SERIES 2000 AUTO |
| SLIDING GLASS DOOR, NOA 02-0221.03, |
| +-67, ONLY WHERE WATER INFILTRATION |
| IS NOT NEEDED, COMPLIANT FOR ZONE 4 |
| ONLY. |
| |
| PLEASE PROVIDE A SCHEDULE OF THE ABOVE, |
| INDICATING ZONE LOCATION AND NOTE THAT |
| WATER INFILTRATION IS NOT NEEDED |
| AS APPLICABLE. |
| |
| 3.)PLEASE RESUBMIT THE POOL ENCLOSURE |
| AS A REVISION.BE ADVISED THAT THIS |
| MUST BE APPROVED BEFORE COMMENCING |
| WORK OR A 4X FEE MAY BE ASSESSED. |
| |
| CC:DON NEELY |