Plan Review Notes For Permit 02060381 |
Permit Number |
02060381 |
|
Review Stop |
B |
Sequence Number |
54 |
|
Notes |
Date |
Text |
2004-06-14 00:00:00 | ****CORRECTIONS**** | | MORSE CALCULATIONS | | | | SAMANTHA HILL, BUILDING PLANS EXAMINER | | [email protected] | | | | 1.)ALL COPIES ARE REQUIRED TO BE | | SIGNED, SEALED AND DATED FAC61G15-23.002 | | PLEASE SUBMIT ORIGINALS,NOT PHOTOCOPIES. | | | | 2.)VARIOUS CALCS WERE GIVEN.IT | | APPEARS THAT THREE DIFFERENT ISSUES | | ARE BEING ADDRESSED.PLEASE INDICATE | | WHAT THE CALCS ARE FOR, REFERRING BACK | | TO THE PLAN (SHOW THE LOCATION USING | | SHEET NUMBERS AND GRIDLINES). | | | | 3.)STRESS INCREASE FOR STEEL IS NOT | | PERMITTED PER FBC1609.4.3(2) WITH LOAD | | COMBINATIONS OF 1609.4.1 OR 1609.4.2. | | PLEASE PROVIDE CLARIFICATION FOR USING | | THE STRESS INCREASE (SHEATHING, PIPE | | CALCS). | | | | 4.)IT IS NOT CLEAR HOW YOU HAVE | | ARRIVED AT THE 170 PSF DESIGN (125, 20, | | 20 = 165) FOR THE HOT WATER TANK, PLEASE | | CLARIFY. |
|